with current and voltage input signals, scaling is required (see chapter 5.3)
Configuration level
Operating manual MIR-491
27
Configuration parameters
Name
Value range Description
Default
9
thermocouple type E (-100...1000°C), NiCr-CuNi
10
thermocouple type B (0/100...1820°C), PtRh-Pt6%
18
special thermocouple
20
Pt100 (-200.0 ... 100,0 °C)
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 200.0 °C)
23
KTY 11-6 (special 0...4500 Ohm)
24
special 0...450 Ohm
30
0...20mA / 4...20mA
1
41
special 0...100 mV
1
50
potentiometer 0...160 Ohm
51
potentiometer 0...450 Ohm
52
potentiometer 0...1600 Ohm
53
potentiometer 0...4500 Ohm
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL
level)
2
2-point correction (at
CAL
level)
3
Scaling (at
PArA
level)
4
Automatic calibration (DAC)
In.F
-1999...9999
Alternative value for error at INP3
OFF
fAI3
Forcing INP3
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
Lim
Name
Value range Description
Default
Fnc.1
Function of limit 1
1
0
switched off
1
measured value monitoring
2
Measured value moni alarm status storage. A stored
limit value can be reset via error list,
è
-key,
Ò
-key or a
digital input ( ->
LOGI
/
Err.r
)
Src.1
Source of imit 1
1
0
process value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
3
measured value INP1