ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
26
4 bis 20 mA
For the following graphic “min Range” is used for 0 % and “max Range” is used for 100 %.
Value
Current
Empty pipe
3.5 mA
Smaller -1.2 %
3.8 mA
Between -1.2 % and 0 %
Linear interpolation from 3.8 mA to 4 mA
0 % (min range)
4 mA
Between 0 % and 100 %
Linear interpolation from 4 mA to 20 mA
100 % (max range)
20 mA
Between 100 % and 102.5 %
Linear interpolation from 20 mA to 20.4 mA
Bigger 102.5 %
22 mA
Behavior of the thermocouple
The integrated thermocouple has no direct contact to the liquid and is used to calculate the expansion
of the housing. The environment temperature has a big influence on the measured temperature of
the thermocouple. The response time of temperature changes is very high caused by the mounting
position of the thermocouple inside the housing.
Step-response time
Step-response time after a significant temperature change. (Filter „Off“)
Summary of Contents for Flowcont UN
Page 30: ......