10
4
black
Digital output Q2
Functions:
1. Empty pipe detection
2. Pulse
3. Threshold monitoring
4. Negative flow 5.Negativ
Fluss
Digital output Q2
Can be freely set in the range of
0.1 to 3000 ml/
pulse in stages of 0.1 ml/pulse,
npn or pnp transistor,
max. load 18 ... 30 V / 100 mA.
Programmable output of 0 V or
24 V when
measuring tube is empty.
Programmable output of 0 V or
24 V when a preset
threshold is exceeded or not
reached.
Programmable output of 0 V or
24 V during
negative flow.
5
grey
Analog output QA
Functions:
1. Flow
2. Temperature
4 ... 20 mA; 0 ... 20 mA
For example: 0 l/min => 4 mA
36 l/min => 20 mA
Alarm => 3,5 mA
(dependent on set measuring
area)
6
pink
Communication
Communication interface
7
purple
Digital input IN1
1. Dosing input
2. Offsett compensation
3. Reset counter
4. Creeping flow
Digital input IN1
Starts the dosage by a rising
edge of 24V.
The Offset is set by a rising
edge of 24V.
Reset of the counter by a rising
edge of 24V.
Creeping suppression is
deactivated as long as
there are 24V at the input
8
orange
No function