Digital input IN1

The Flowcont UN has a digital input that is programmable to following functions: dosing input, set 

offset, creeping suppression inactive and reset counter. In order to start a dosing process, wiring to 

24V DC is required. The condition is the configuration of the dosing parameters with the user display. 

Dosing input is debounced so that re-start is not possible during a running dosing process. After 

changing configurations a restart of the device is needed to activate the function.

Example Dosing

Dosing can basically be realized in two ways:

1. The Flowcont UN as dosing device (dosing control Flowcont UN)

The Flowcont UN does the entire dosing control. The dosing quantity (e.g. 400 ml) is pre-set in the 

FFU using the user menu of the display. Dosing starts, as soon as line digital input is wired to 24 

V, e.g. via a pushbutton. FFU will now open the dosing valve via the output configured for it. When 

the pre-set dosing quantity is reached, the dosing valve is closed via the above output. The dosing 

procedure can also be started and stopped by using the dosing user menu. The 2nd output can be 

used independently for signaling of empty pipe detection, limit control or flow direction.

The following settings are necessary:

Adjustment of dosage in the menu

Dosing 

 Dosing quantity 

 400 ml

Setting the max. dosing time that should be allowed for safety reasons.

Digital Input I1 

 Dosing

Digital Output Q1/Q2 

 Function 

 Dosing

2) Flowcont UN as flow meter (dosing control via dosing equipment)

The dosing equipment is responsible for the entire dosing control. Therefore, the dosing quantity is 

fixed in the dosing equipment control during commissioning by pre-selecting the meter pulses. Dosing 

starts, when the relevant pushbutton of the dosing equipment is pushed. The control will now open 

the dosing valve. From now on FFU will send a voltage pulse to the control for each volume unit that 

has flown through (e.g. per 1ml). When the pre-selected pulse quantity is reached, the control closes 

the dosing valve. In this case, output Q1/Q2 is used to send out pulses.

The following settings are necessary:

Adjustment of puls output in the menu

Digital Output Q1/Q2 ==> Function ==> Pulse Output

Options Output ==> Pulse Value ==> e.g. 1 ml per pulse.

Summary of Contents for Flowcont UN

Page 1: ...an hygienic version available EHEDG approved and FDA compliant CIP Maintenance free flow sensor saving maintenance costs Adjustable ranges reduces variants Can be used for conducting and non conductin...

Page 2: ...us The actual technical manual includes instructions for installation electrical connection and inauguration as well as the technical data of the device Modifications that answer the purpose of the te...

Page 3: ...Index Principle of operation 4 Safety notes 4 Applications 4 Commissioning 5 Installation notes 5 Mounting 6 Electrical connection 8 Operation 11 Commissioning procedure 11 Display and menu 11 Overvie...

Page 4: ...e Flowcont UN is not a safety module according to the EU Machinery Directive Observe the national safety and work safety regulations Repairs may only be carried out by the manufacturer Changing or alt...

Page 5: ...red liquid it can be helpful to have sufficient backpressure on the outlet Flowcont UN If any solid particles are present this can lead to measurement errors When pumps are used the flow sensor must b...

Page 6: ...f gas bubbles in the Flowcont UN measuring channel will aid optimal measurements For applications with a Clean Design when complete drain of the measuring tube is needed we recommend to mount the flow...

Page 7: ...rolsystem de 7 Application with hot fluids In applications where the Flowcont UN is subject to high heat t 60 C we recommend mounting the measuring device and electronic housing beneath the measuremen...

Page 8: ...the current measured value Connection diagram 5 pin variant Pin Wire colour Function Description 1 brown L Supply voltage 18 V DC 30 V DC 2 white Digital output Q1 Functions 1 Pulse 2 Empty pipe detec...

Page 9: ...brown L Supply voltage 18 V DC 30 V DC 2 white Digital output Q1 Functions 1 Pulse 2 Empty pipe detection 3 Dosing output 4 Threshold monitoring 5 Negative flow Digital output Q1 Can be freely set in...

Page 10: ...of 0 V or 24 V when a preset threshold is exceeded or not reached Programmable output of 0 V or 24 V during negative flow 5 grey Analog output QA Functions 1 Flow 2 Temperature 4 20 mA 0 20 mA For ex...

Page 11: ...pin variant Digital output 1 Q1 function and behavior Digital output 2 Q2 function and behavior Analog output QA Flow range for current output Pulse value Creeping suppression Digital input IN1 Displ...

Page 12: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 12 Menu...

Page 13: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 13...

Page 14: ...gnal reacts slower when average determination is strong Units The Flowcont UN is able to show actual flow or the volume in different unities Following unities can be selected ml s l Gal min Gal l min...

Page 15: ...min for DN25 Diagnostic The sub menu Diagnostic shows the actual software hardware version and many helpful values for analysis Knowing about the actual values or the state bits makes it easy to revi...

Page 16: ...requency of the control Example 2 0 ml pulse This means a pulse is emitted every 2 0 ml Setting range 0 1 3000 0 ml pulse in 0 1 ml pulse steps Default setting 1 0 ml pulse Digital output Q1 Digital o...

Page 17: ...he dosing valve is closed via the above output The dosing procedure can also be started and stopped by using the dosing user menu The 2nd output can be used independently for signaling of empty pipe d...

Page 18: ...sion 0 3 l min at NW10 0 9 l min at NW15 3 5 l min at NW20 5 0 l min at NW25 General instructions The following checks should be carried out before the measuring device is switched on for the first ti...

Page 19: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 19 Dimensional drawing...

Page 20: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 20...

Page 21: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 21...

Page 22: ...l min Inlet zone 10 cm 30 cm 50 cm 80 cm Outlet zone 0 cm 5 cm 10 cm 20 cm Conductivity No limitation Accuracy 2 2 of final value optional 1 of reading 3 mm s Reproduzierbarkeit 0 5 Aufl sung 0 003 l...

Page 23: ...direction 1 analog output 4 mA 20 mA 0 mA 20 mA current flow and temperature 2 pulse status output PNP transistor output for flow rate meter empty pipe detection flow monitoring dosing output flow di...

Page 24: ...PNP normally closed High impedance High impedance 24 V pulse PNP normally open High impedance High impedance 24 V pulse Lower limit output Below lower limit Between the limits Above upper limit NPN n...

Page 25: ...NPN normally open High impedance 0 V High impedance PNP normally closed High impedance High impedance 24 V PNP normally open High impedance 24 V High impedance Characteristic analog output 0 20 mA For...

Page 26: ...4 mA to 20 mA 100 max range 20 mA Between 100 and 102 5 Linear interpolation from 20 mA to 20 4 mA Bigger 102 5 22 mA Behavior of the thermocouple The integrated thermocouple has no direct contact to...

Page 27: ...perature In the table below some examples of the temperature influence are shown Liquid temperature x 0 7 Enviroment temperature x 0 3 Measured temperature 40 C x 0 7 20 C x 0 3 34 C 40 C x 0 7 30 C x...

Page 28: ...quired After restart the changes are active Available input functions Set offset Creeping flow off Dosing Reset counter off 0 V Rising edge 0 24 V Set offset6 State Switch creeping flow off Positive e...

Page 29: ...sidue of measured materials Failed devices can only be examined when accompanied by a completely filled out return form Such a declaration includes information about all materials which have come into...

Page 30: ......

Reviews: