Vertu Series VPM3000 Process Meters & Temperature Transmitters
Instruction Manual
41
Factory Defaults & User Settings
The following table shows the factory setting for most
of the programmable parameters on the meter. Next
to the factory setting, the user may record the new
setting for the particular application. DisplayWizard
software allows the saving of all meter parameters to
a file for restoring meter settings, reporting, and
copying settings to other meters.
Model: ______________ S/N: _______________
Date: _______________
Parameter
Display Default
Setting
User
Setting
Input type
inpt
4-20 mA
Decimal point
dd.dd
2 places
Programming
prog
Input 1
InP1
4.00 mA
Display 1
Dis1
4.00
Input 2
InP2
20.00 mA
Display 2
Dis2
20.00
Relay 1
Rly1
Action 1
Act1
Automatic
Set 1
Set1
7.00
Reset 1
RSt1
6.00
Relay 2
Rly2
Action 2
Act2
Automatic
Set 2
Set2
10.00
Reset 2
RSt2
9.00
Fail-safe
flsf
Fail-safe 1
Fls1
Off
Fail-safe 2
Fls2
Off
Time delay
dlay
On delay 1
On1
0 sec
Off delay 1
Off1
0 sec
On delay 2
On2
0 sec
Off delay 2
Off2
0 sec
Parameter
Display Default
Setting
User
Setting
Break 1
Brk1
Off
Break 2
Brk2
Off
Password
pass
0000
(unlocked)
Advanced
Features
N/A
Adjust
Adj
0.0
°
(temp
only)
Filter
fltr
10
Bypass
byps
0.2
Serial settings
serl
Protocol
pdC
PDC
protocol
Address
addr
00
Baud rate
baud
2400
Trans delay
trde
10 ms
Function
Func
Linear
Cutoff value
CutF
0.00
(disabled)
Output option
out
/
Aou
t
Factory set
only
Display
intensity
inty
Level 8
Modbus
defaults
N/A
Address
addr
247
Parity
prty
Even
Byte-to-byte
timeout*
tbyt
0.01 sec
*Note:
The byte-to-byte timeout setting might be updated
automatically depending on the baud rate selected
and the previous timeout setting. The minimum
timeout allowed is saved to memory if a lower value is
entered (e.g. If user enters 0.00 with a baud rate of
300, 0.06 is saved)