Power 

 

Connect power at TB3-1 (+) and 
TB3-2 (-). 

 

CAUTION:

  A terminal voltage at or 

above 6V min should be maintained 
to the unit during operation.  Do 
not exceed 36VDC peak to avoid 
damage to the unit.   

 

Observe proper polarity.  Reverse 
voltage protection up to 60V is 
built-in.  Your supply should be 
rated at twice the maximum 
current draw to allow for potential 
inrush current. 

 

Connect 6-32V DC SELV (Safety Extra Low Voltage), up to 2.1W including input 
module.  Your current draw will be dependent on your choice of input module, 
whether you use one or both splitter output channels, output current or voltage, 
voltage load, and AUX load.  You can approximate power consumption by 
combining power of major features you are using and this applies quite well for 
voltage levels from 9-32V (multiply this by 1.07 below 9V).  A uB41 module is 
represents a standard load, and a uB42 represents the largest module load. 

 

POWER FEATURE 

TYP REQD POWER AT SUPPLY 

uBSP-P-1 Splitter w/o Module 

0.44W 

+uB41 Input Module (Standard Load) 

0.29W 

..or uB42 Input Module (Maximum Load) 

0.66W 

+Current Output at 4mA

1

 

0.08W each 

  or Current Output at 20mA

1

 

0.40W each 

+5mA AUX Voltage Output (10V/2KΩ)

 

0.06W 

+Voltage Output of 10V into 2KΩ

 

0.12W 

MAX TOTAL w/uB41or equivalent 

1.59W Typical 

MAX TOTAL w/uB42 or equivalent 

1.96W Typical 

1

Note

: Incremental power consumption of current output is ~0.02W/mA. 

 

 

 

POWER REQUIRED BY FEATURE 

BY MODULE 

TYP 

MODEL 

BASE 

V-OUT 

I-OUT 

AUX  uB41  uB42 

Ptot 

uBSP-P-1/uB41 

0.44 

0.12 x2  0.40 x2  0.06 

0.29 

0.68 

1.59 

uBSP-P-1/uB42 

0.44 

0.12 x2  0.40 x2  0.06 

0.29 

0.66 

1.96 

 

 

 
The rightmost column represents typical input power with a 9-32V supply, a 
module installed, and full-scale outputs.  For voltage below 9V, multiply Ptot by 
1.07.  To calculate current draw, divide Ptot for your splitter/module/feature 
combination by your supply voltage to get typical current ±5% for loaded 
conditions (see Table 3 below for computed values).   

 

Power...

 

 
Note:

  It is recommended that 

supplies capable of supplying more 
than 2.5A to the carrier be fused 
with a surge tolerant fuse. 
 
Choose a fuse rated for 2x current.  
Limit maximum fuse rating below 
3A Supplies capable of supplying 
more than 2.5A to a carrier should 
be fused with a surge tolerant fuse

 

 
Multiply current by 1.1 for maximum current.  Current provided below assume a 
loaded carrier with uB module installed, full-scale output currents, and AUX 

voltage output loaded w/1KΩ.

 

 

Table 3 

uBSP-P-1 Current Draw 

uBSP-P-1 Current Draw 

POWER 

w/Standard uB41 Module 

w/Loaded uB42 Module 

SUPPLY 

TYP 

MAX 

TYP 

MAX 

6V 

284mA 

312mA 

350mA 

384mA 

9V 

177mA 

194mA 

218mA 

240mA 

12V 

133mA 

146mA 

163mA 

180mA 

15V 

106mA 

117mA 

131mA 

144mA 

24V 

66mA 

73mA 

82mA 

90mA 

32V 

50mA 

55mA 

61mA 

67mA 

 

Power Supply Effect: 

 Less than 

0.001% of output span effect per volt DC 

change. 

 

 

Summary of Contents for microBlox uBSP-P-1

Page 1: ...uB Field Input Modules USER S MANUAL ACROMAG INCORPORATED Tel 248 295 0880 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 2417 U S A email sales acromag com Copyright 2018 Acromag Inc Printed...

Page 2: ...ections Each Splitter Output Supports Voltage or Current 11 AUX Voltage Output Connections 12 CONFIGURATION SOFTWARE 12 CONFIGURATION SOFTWARE 13 Quick Overview Android Reconfiguration 13 Quick Overvi...

Page 3: ...or human life is involved It is important that you perform satisfactory overall system design and it is agreed between you and Acromag that this is your responsibility The information of this manual...

Page 4: ...lox module carrier adds wide input isolated power cold junction compensation for thermocouple modules dual isolated current and or voltage outputs an AUX voltage output plus LED indication for module...

Page 5: ...than 0 1 output accuracy Wide ambient temperature operation from 40 C to 75 C All I O and power ports are transient protected Wide range isolated DC power input from 6 32V LED indicators for module B...

Page 6: ...a Windows based personal computer laptop or a wired USB OTG connection to an Android smartphone tablet This carrier provides isolated host power to the module a host USB port a host voltage output th...

Page 7: ...nd lift it from the rail To attach the carrier to T type DIN rail position the top groove of the DIN Clip along the rail and push the bottom inward to snap it into place on the DIN rail To remove it f...

Page 8: ...te 16 26 AWG 1 31 0 13mm2 solid or stranded wire with a minimum temperature rating of 85o C Input wiring may be shielded or unshielded type twisted pair or shielded twisted pair input wiring is recomm...

Page 9: ...function as a simple single channel I O carrier for Bluetooth wireless technology modules and you may configure a B module on this carrier to drive its single AUX output using Bluetooth wireless techn...

Page 10: ...ual 8501 043 uB34 2 3 Wire uB35 4 Wire RTD Input User s Manual 8501 044 Introduction to Agility Configuration Tool for microBlox 8501 047 uB37 uB47 TC Input User Manual 8501 050 uB04 uB08 uB16 Back Pa...

Page 11: ...ected in their connection diagrams for the specific plug in module model Ground connections noted are recommended for best results and help protect the unit and its isolated circuits by giving each is...

Page 12: ...ers laptops or a USB OTG connection to Android smartphones tablets with the Agility APP The Windows USB software for your model operates like the Agility APP software Below is a brief introduction to...

Page 13: ...he device indicated to the right of Selected Device and move to the main portion of the app shown in the second screen at left Note Android requires user permission to access external hardware If the...

Page 14: ...nostic exchange and review the results returned If one or more tests indicate Failed you can also tap the down arrow message below the self test report to access additional information regarding faile...

Page 15: ...akin to a power on reset of the splitter You can tap RESET FACTORY CALIBRATION to get out of trouble if you ever miscalibrate a splitter this only affects splitter calibration You can tap RESTORE FAC...

Page 16: ...ents Input calibration controls first followed by Output calibration controls as you scroll down the page IMPORTANT The splitter has had its input output channels factory calibrated with high precisio...

Page 17: ...our output range For Full Scale calibration use the output adjustment slider and the coarse and fine adjustment controls to precisely set your output full scale level while precisely monitoring your o...

Page 18: ...The input type of the plug in module is shown at the top of the screen actual input value not the scaled input value is polled Select the Indicator pointer to set your desired indication to Digital v...

Page 19: ...nication Set up I O Config Test and Calibration A short description of each of these pages follows This section is used to select a connected transmitter and open close communications with it Device c...

Page 20: ...ich output of this splitter you are calibrating Input First set the Input Range to calibrate in the I O Config Test page and be sure to click the Send I O Config button before attempting calibration O...

Page 21: ...us feature of the uBSP P 1 splitter and its USB software is that it allows all versions of microBlox input modules to be reconfigured using a wired USB connection both B and fixed range uB models exce...

Page 22: ...range zero full scale endpoints I O scaling in a channel can be done in reverse to produce a reverse acting output signal Refer to the block diagram to gain a better understanding of how this splitter...

Page 23: ...fect on standard microBlox modules Unit Fails to Start up or Initialize Check power voltage level and capacity making sure that it is at least 6V and of sufficient capacity select a current capacity 2...

Page 24: ...Check CJC Setting Refer to your module specifications and determine the required CJC status for your model Enable or disable CJC as required for your module by setting the channel CJC DIP switch acco...

Page 25: ...his isolator and cable are also included in TT SIP see above USB A B Cable USB A B Cable Order 4001 112 This is a 1 meter USB A B replacement cable for connection between your PC and the USB isolator...

Page 26: ...fer to your plug in module instructions for wiring Accuracy Better than 0 05 of span typical relative to the installed module plus an additional 0 05 of span relative to its operation on this carrier...

Page 27: ...12 20mA 20mA 59577 5 0V 10 0V 62556 5 0V 10V 65535 5 5V 11 0V 5 5V 11V 24mA 24mA RES 1 59577 1 59577 1 59577 1 59577 1 54612 1 43689 1 lsb 83 925uV 167 8uV 167 8uV 335 7uV 0 34132uA 0 34132uA Span 0 0...

Page 28: ...sourced from module Channel BLE Blue Channel Blue ON indicates Linking to channel is enabled for uBxx B Bluetooth wireless technology enabled models via the BLE DIP switch of the channel This LED is...

Page 29: ...o an Android smartphone tablet The USB interface is used to configure and calibrate the input of the module plugged into this carrier and each output of this splitter Because the input module power an...

Page 30: ...equivalent 1 59W Typical MAX TOTAL w uB42 or equivalent 1 96W Typical 1 Note Incremental power consumption of current output is 0 02W mA POWER REQUIRED BY FEATURE BY MODULE TYP MODEL BASE V OUT I OUT...

Page 31: ...ses Operating Temperature 40 C to 75 C 40 F to 158 F Storage Temperature 40 C to 85 C 40 F to 185 F Relative Humidity 5 to 95 non condensing Isolation Input field isolation is provided by the plug in...

Page 32: ...than pollution degree 2 as defined in EN IEC 60664 1 2 The equipment shall be installed in an enclosure that provides a degree of protection not less than IP 54 and only accessible with the use of a t...

Reviews: