Model DT333-0700
4-Wire mV/TC Dual Transmitter w/USB
Acromag, Inc. Tel: 248-295-0880
- 14 -
http://www.acromag.com
- 14 -
https://www.acromag.com
Quick Overview
–
Windows
Click
“Open”
to connect to the DT333-0700 and your
screen will like:
HELP
–
press F1 for Help on a selected or highlighted field or
button. You can also click [?] in the upper-right hand corner of
the screen and click again to point to a field or button to get a
Help message pertaining to the item you pointed to.
For detailed configuration and calibration procedures, see the
Operation Step-By-Step section of the Technical Reference on
page 18 of this manual.
This transmitter can be
reconfigured and calibrated via
its USB Configuration Software
and a USB connection to your
Windows PC or laptop. The
software can be downloaded
and
is included on a CDROM bundled with the
Configuration Kit TTC-SIP (see Accessories section).
For this model, look for program DT333Config.exe.
This software is compatible with v7 or later versions of
the Windows operating system.
The initial USB configuration software screen for this
model is shown at left. Unit configuration information
is divided across four separately tabbed pages as
follows: Communication Set up, Configuration,
Calibration, and Diagnostics. A short description of
each of these configuration pages follows:
Communication Set up (First Connect to Unit Here)
•
Select from connected transmitters and
Open/Close communication with them.
•
Display the Model, Serial Number, and
Manufacturer of the connected transmitter and
report the status of communication with it.
Configuration (Configure and/or Test the Unit Here)
•
Click
[Get I/O Config]
to retrieve the I/O
configuration of the current connected unit.
•
Select the operating Mode: Dual transmitter,
Single transmitter, or Signal Splitter.
•
Set Input type/range: J,K,T,R,S,E,B,N, or ±100mV.
•
Set the level of digital filtering to High, Medium,
Low, or None (No digital filter). I/O response
times vary with filter and are indicated next to
your selection (see Specifications for details).
•
Set the Break Detection Upscale or Downscale.
•
Turn CJC on/off for the channel.
•
Set the current or voltage Output Range to ±10V,
±5V, 0-5V, 0-10V, ±20mA, 0-20mA, or 4-20mA.
•
View the unit’s configuration message status in
the Status field.
•
Use the I/O Scaling fields to specify the input
range endpoints to correspond to the nominal
output range zero and full-scale endpoints (some
over/under-range is included).
•
After making changes, send your settings to the
unit by clicking
[Send I/O Config]
and follow the
on-screen prompts.