20
01D1H _
465
Over voltage alarm threshold
2
R/W
Integer
Unit 0.1V
01D2H _
466
Over voltage alarm delay
2
R/W
Integer
Unit 0.01S
01D3H _
467
Undervoltage alarm threshold
2
R/W
Integer
Unit 0.1V
01D4H _
468
Undervoltage alarm delay
2
R/W
Integer
Unit 0.01S
01D5H _
469
Overcurrent Alarm Threshold
2
R/W
Integer
Unit 0.01A
01D6H _
470
Overcurrent Alarm Delay
2
R/W
Integer
Unit 0.01S
01D7H _
471
Undercurrent alarm threshold
2
R/W
Integer
Unit 0.01A
01D8H _
472
Undercurrent alarm delay
2
R/W
Integer
Unit 0.01S
01D9H _
473
Over power alarm threshold
2
R/W
Integer
Unit 0.001kw
01DA H
474
Over power alarm delay
2
R/W
Integer
Unit 0.01S
01DB H
475
Under power alarm threshold
2
R/W
Integer
Unit 0.001kw
01DC H
476
Under power alarm delay
2
R/W
Integer
Unit 0.01S
01DD H
477
DI1 initial state
2
R/W
0: Normally open
1: Normally closed
01DE H
478
DI1 programming
2
R/W
0: Do not associate with
DO
1: Associate DO1
2: Associate DO2
01E5H _
485
DO1 output mode
2
R/W
0: level
1: Pulse
01E6H _
486
DO1 related content
2
R/W
0: Normal DO
1: total failure
2: Total fault +DI1+DI2 3:
DI1
4:DI2
5:DI1+DI2
01E7H _
487
DO1 output pulse width
2
R/W
0: none
1:1S
2:2S
3:3S
4:4S
5:5S
Summary of Contents for ADW310