19
start
address
(hexadeci
mal)
initial address
(decimal)
data item name
length
(bytes)
read/
write
Remark
01EBH
491
Alarm 1 state
2
R
bit0: Over voltage alarm
bit1: under voltage alarm
Bit2: Overcurrent alarm
Bit3: undercurrent alarm
Bit4: Over power alarm
Bit5: Under power alarm
Bit6: Whether DO1 alarm
output
bit7: Whether DO2 alarm
output
Bit8:
Bit9:
Bit10:
Bit11:
Bit12:
Bit13:
Bit14:
Bit1 5 : Power off report
01DOH
464
Alarm 1 enable bit
2
R/W
Bit0: Overvoltage alarm
enable bit
Bit1: Undervoltage alarm
enable bit
Bit2: Overcurrent alarm
enable bit
Bit3: Undercurrent alarm
enable bit
Bit4: Over power alarm
enable bit
Bit5: Under-power alarm
enable bit
Bit6: Whether DO1 alarm
output
bit7: Whether DO2 alarm
output
Bit8:
Bit9:
Bit10:
Bit11:
Bit12:
Bit13:
Bit14:
Bit1 5 : Power- off report
enable bit