13
101FH
Voltage shield
2
R/W
0~655.35%
1020H
Current shield
2
R/W
0~655.35%
1021H-1025H
reserved
1026H
demand cycle
2
R/W
Unit min (
1-30)
1027H-102DH
reserved
102EH
Backlight time
2
R/W
0: always on 1: 1min
2:2min
102FH
time
10
R/W
Year,
Month Day,
week, hour,
minutes, seconds,
millisecond
1034H-1035H
reserved
1036H
DO status
2
R/W
Bit0: DO1 Bit1: DO2...
0: open
1: closed
1037H
DI status
2
R
Bit0:DI1 Bit1:DI2...
0: open
1: closed
1038H
First time zone timetable number
first time zone start month, first time
zone day
Second time zone timetable number
Second time zone start month, second
time zone day
Third time zone timetable number
3rd time zone start month, 3rd time
zone day
Fourth time zone timetable number
4th time zone start month, 4th time zone
day
Fifth time zone timetable number
Fifth time zone start month, fifth time
zone day
Sixth time zone timetable number
6th time zone start month, 6th time zone
day
Seventh time zone timetable number
7th time zone start month, 7th time zone
day
Eighth time zone timetable number
Eighth time zone start month, eighth
time zone day
12
R/W
Time slot number:
period 1,
period 2,
period 3,
period 4,
Start month: 1-12
Start day: 1-31
1044H
The first set of timetables,
Each period occupies three bytes,
R/W
Rate: 0
1 point, 2 peaks
Summary of Contents for ADW310