15
Unit kVar
3 decimal places
Analyze the same active
power
201EH-2023H
reserved
2024H
inspecting power
4
R
Integer
Unit KVA
3 decimal places
Analyze the same active
power
2026H-202BH
reserved
202CH
power factor
4
R
Integer
3 decimal places
If the value is 999,
Then the
value=999*0.001=0.999
202EH-2033H
reserved
2034H
frequency
4
R
Integer 2 decimal places
If the value is 5000 ,
Then the value = 5000
*0.01= 50.00H
2036H-
reserved
2058H
temperature 1
4
R
Integer signed
Unit 0.1
℃
205AH
temperature 2
4
R
Integer signed
Unit 0.1
℃
3000H
Secondary value of total active energy
4
R/W
Two decimal places, Kwh
3002H
Secondary value of forward active
energy
4
R/W
Two decimal places, Kwh
3004H
Secondary value of reverse active
energy
4
R/W
Two decimal places, Kwh
3006H
Secondary value of total reactive energy
4
R/W
Two decimal places, Kvarh
3008H
Secondary value of forward reactive
energy
4
R/W
Two decimal places, Kvarh
300AH
Secondary value of reverse reactive
energy
4
R/W
Two decimal places, Kvarh
300CH
reserved
300EH
Total active energy peak secondary
value
4
R/W
Integer, unit kWh
2 decimal places
If the value is 120201, P
T=10 , CT=10;
Then value = value * P
T*CT=
120201*0.01*10*10=12020
3010H
Total active energy peak secondary
4
R/W
Integer, unit kWh
Summary of Contents for ADW310