18
Then value = value * P
T*CT=
120201*0.01*10*10=12020
302CH
Reverse reactive energy peak
secondary value
Reverse reactive energy peak
secondary value
4
R/W
Integer, unit kWh
2 decimal places
If the value is 120201, P
T=10 , CT=10;
Then value = value * P
T*CT=
120201*0.01*10*10=12020
302EH
Reverse reactive energy level
secondary value
4
R/W
Integer, unit kWh
2 decimal places
If the value is 120201, P
T=10 , CT=10;
Then value = value * P
T*CT=
120201*0.01*10*10=12020
3030H
Reverse reactive energy valley
secondary value
4
R/W
Integer, unit kWh
2 decimal places
If the value is 120201, P
T=10 , CT=10;
Then value = value * P
T*CT=
120201*0.01*10*10=12020
3032H-
reserved
4006H
Total active power real-time demand
4
R
Integer, unit kW
3 decimal places
400CH
Total forward active power real-time
demand
4
R
Integer, unit kW
3 decimal places
400EH
Total reverse active power real-time
demand
4
R
Integer, unit kW
3 decimal places
4010H
Total forward reactive power real-time
demand
4
R
Integer, unit kW
3 decimal places
4012H
Total reverse reactive power real-time
demand
4
R
Integer, unit kW
3 decimal places
4014H-
reserved
01D0H-01EBH
Alarm 1 related data, see chapter 6.3.1 for details
0216H-0249H
Alarm 2, alarm 3 related data, see chapter 6.3.2 for details
0268H-0169H
Alarm 2, Alarm 3 alarm status, see chapter 6.3.2 for details
6.3 Alarm function related settings
6.3.1 Alarm 1 related parameter register address table