10
4.4 Temperature measuring terminal
temperature input
4.5 Wiring Instructions
5 Main Features
5.1 Measurement function
It can measure all power parameters including voltage U, current I, active power P, reactive power Q,
apparent power S, power factor PF, phase angle Φ between voltage and current, frequency F, 31st
harmonic, parity Total harmonic content and total harmonic content. Among them, the voltage U has 1
decimal place, the frequency F has 2 decimal places, the current I has 3 decimal places, the power P has 4
decimal places, and the phase angle Φ has 2 decimal places.
Such as: U = 220.1V, f = 49.98HZ, I = 1.999A, P = 0.2199KW, Φ= 60.00° .
Support 2 -way temperature measurement, temperature measurement range: -40 ~ 99 °C, accuracy ±2 °C
Summary of Contents for ADW310