Replace the outdoor mainboard
YES
F5 Malfunction of Wired Controller Temperature Sensor
H6 Malfunction of Outdoor Fan Motor
Replace the outdoor fan motor and
then restart the unit to see if there
still is malfunction of outdoor fan
motor
Malfunction of outdoor fan motor
Correctly connect the
control wire of fan
motor on the mainboard
Operate the unit with
the new motor
Check if the control wire of
outdoor fan motor is connected on
the outdoor mainboard correctly
YES
NO
NO
Malfunction of wired controller
temperature sensor
Replace the wired
controller