Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
address sequence and then press Enter/Cancel button to confirm. The setting value will be memorized
after power failure. The detailed setting is as shown in the Figure below:
Figure 2-7-13
When the address is set, the wired controller can be removed and connect the centralized controller to
the indoor main board. Then connect the required units to realize centralized control of these units
;
Notes:
When centralized controller is to be connected, set the address mode into centralized
controller address mode through wired controller. Long-distance control address mode can
not be set;
The unit addresses in the same network must be different, otherwise, communication
malfunction will occur and the unit can not work normally;
When centralized controller is to be connected, the unit address range is 1 -16. Only 16 sets
of unit in maximum can be connected
The code and model of wired controller is as below:
Name
Product code
Remark
Centralized controller
CE50-24/E
MC207025
Only 16 sets of unit in maximum can be connected to
this controller
When the address is set, the wired controller can be removed and connect the centralized controller to the indoor main board.
Then connect the required units to realize centralized control of these units;
Notes
1. When centralized controller is to be connected, set the address mode into centralized controller address mode through
wired controller. Long-distance control address mode can not be set;
2. The unit addresses in the same network must be different, otherwise, communication malfunction will occur and the unit
can not work normally;
3. When centralized controller is to be connected, the unit address range is 1-16. Only 16 sets of unit in maximum can be
connected
4. The code and model of wired controller is as below:
Name
Product code
Remark
Centralized controller
CE50-24/E
MC207025
Only 16 sets of unit in maximum can be connected to this controller
7.2.5 Light board control:
Light board interface is reserved on the main board of duct type unit. You can purchase Gree light board to realize control of
the unit. When wired control is also connected, you can realize control of the unit through light board and wired controller.
Light board information:
Name
Product code
Remark
Receiving board Z6L
30260000001
Only for duct type unit