Technical Information
U-Match Series DC Inverter Service Manual
85
an oil bend should be employed for every 6m (19-2/3 feet).
Oil bend
Indoor
Outdoor
6m
(19
-2/
3f
ee
t)
Oil bend
Figure 3-3-8
3.2 Specification of Connection Pipe
Table 3-3-3
Item
Model
Size of Fitting Pipe
mm (inch)
Max. Pipe
Length
m (feet)
Max. Height Difference
between Indoor Unit and
Outdoor Unit
m (feet)
Drainage pipe(Outer
Diameter × wall
thickness)
mm (inch)
Liquid
Gas
GUHD18ND3FO
6(1/4)
12.7(1/2)
20(65-3/5)
15(49-1/5)
Φ17
×1.7
5(Φ
5/8 × 7/100)
GUHD24ND3FO
9.5(3/8)
16(5/8)
30(98-2/5)
15(49-1/5)
Φ17×1.75(Φ5/8
× 7/100)
GUHD30ND3FO
30(98-2/5)
15(49-1/5)
Φ17×1.75(Φ5/8
× 7/100)
GUHD36ND3FO
30(98-2/5)
15(49-1/5)
Φ17×1.75(Φ5/8
× 7/100)
GUHD42ND3FO
50(164)
30(98-2/5)
Φ17×1.75(Φ5/8
× 7/100)
GUHD48ND3FO
50(164)
30(98-2/5)
Φ17×1.75(Φ5/8
× 7/100)
The connection pipe should be insulated with proper water-proof insulating material.
The pipe wall thickness shall be 0.5~1.0mm (1/50~1/25inch) and the pipe wall shall be able to
withstand the pressure of 6.0MPa (870psig). The longer the connecting pipe, the lower the cooling and
heating effect performs.
4 ELECTRIC WIRING WORK
4.1 Wiring Precautions
.
Before obtaining access to terminals, all supply circuits must be disconnected.
.
The rated voltage of the unit is as shown as Table 1-4-1 and Table 1-4-2
.
Before turning on, verify that the voltage is within the 187~252V range (for single phrase units).
④
.
Always use a special branch circuit and install a special receptacle to supply po wer to the air conditioner.
⑤
.
Use a special branch circuit breaker and receptacle matched to the capacity of the air conditioner.
⑥
.
The special branch circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles
of the wiring and has an isolation distance of at least 3mm (1/8inch) between the contacts of each pole.
⑦
.
Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
⑧
.
Install a leakage special branch circuit breaker in accordance with the related laws and regulations and electric
company standards.
3.2 Specification of Connection Pipe
Table 3-3-3
Model/Item
Size of Fitting Pipe
mm (inch)
Max. Pipe
Length
m (feet)
Max. Height Difference
between Indoor Unit and
Outdoor Unit
Drainage pipe(Outer
Diameter × wall thickness)
mm (inch)
Liquid
Gas
AUHD18ND3FO
6(1/4)
12.7(1/2)
20(65-3/5)
15(49-1/5)
Φ
17×1.75(
Φ
5/8 × 7/100)
AUHD24ND3FO
9.5(3/8)
16(5/8)
30(98-2/5)
15(49-1/5)
Φ
17×1.75(
Φ
5/8 × 7/100)
AUHD30ND3FO
30(98-2/5)
15(49-1/5)
Φ
17×1.75(
Φ
5/8 × 7/100)
AUHD36ND3FO
30(98-2/5)
15(49-1/5)
Φ
17×1.75(
Φ
5/8 × 7/100)
AUHD42ND3FO
50(164)
30(98-2/5)
Φ
17×1.75(
Φ
5/8 × 7/100)
AUHD48ND3FO
50(164)
30(98-2/5)
Φ
17×1.75(
Φ
5/8 × 7/100)
The connection pipe should be insulated with proper water-proof insulating material.
The pipe wall thickness shall be 0.5~1.0mm (1/50~1/25inch) and the pipe wall shall be able to withstand the pressure of
6.0MPa (870psig). The longer the connecting pipe, the lower the cooling and heating effect performs.
4 ELECTRIC WIRING WORK
4.1 Wiring Precautions
1. Before obtaining access to terminals, all supply circuits must be disconnected.
2. The rated voltage of the unit is as shown as Table 1-4-1 and Table 1-4-2
3. Before turning on, verify that the voltage is within the 187~252V range (for single phrase units).
4. Always use a special branch circuit and install a special receptacle to supply power to the air conditioner.
5. Use a special branch circuit breaker and receptacle matched to the capacity of the air conditioner.
6. The special branch circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the
wiring and has an isolation distance of at least 3mm (1/8inch) between the contacts of each pole.
7. Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
8. Install a leakage special branch circuit breaker in accordance with the related laws and regulations and electric company
standards.
CAUTION!
1. The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances.
When the current contracted capacity is insufficient, change the contracted capacity.
2. When the voltage is low and the air conditioner is difficult to start, contact the power company to raise the voltage.