Installation & Operation Manual
- Model AVT6000
Page C5
Each item that was configured in Step 3 should appear in the list. If any devices
are missing, there may be problem with the physical network or one of the
devices was not configured properly. If only the Totalizer appears on the list,
check the network wiring and verify the 120-ohm termination resistors are
installed on each end of the network. If only one or two items are missing from
the list, plug into those items to confirm they have been properly configured.
If your device has not yet been configured the default device address of 127 will
be shown. The complete device list can
only
be viewed from the valve assigned
as the totalizer valve. All other devices will only show their own individual
Accunet ID information.
Step 6: Setting the Analog Output to Totalizer
6-1.
Connect the pc to the Totalizer AccuValve and open AccuValve Insight.
6-2.
Select the Config Button on the appropriate Analog Output Gauge, the select
ACCUNET and enter the Analog Output Full Scale Range for the total exhaust
airflow in the AccuNet network.
6-3.
Verify the Totalized airflow indicated is equivalent the sum of each of the
airflows from all devices on the AccuNet network.
Select
Select
Enter FS Range for the
Total Exhaust Flow