Installation & Operation Manual

 - Model AVT6000 

Contents of this Manual are Subject to Change Without Notification 

 

Page 13 

4.1

 

Round Valve Installation Diagrams 

Standard Slip-fit Valve Secured to Duct with Tek Screws. NOT ACCEPTABLE FOR PFA COATED 
VALVE.

 

 

 

 

 

 

 

 

 

Standard Slip-fit Valve Secured to Duct with Draw Band Clamps

  

 

 

 

 

 

 

 

 

 

 

 

Flanged Valve “Option –F” Secured to Duct with 

Vanstone Flanges and Hardware 

 

 

 

 

 

 

 

 
 

 

 

INLET 

DISCHARGE 

Locate duct supports within 12” of each end of the valve.

 

 

Locate duct supports within 12” of each end of the valve.

 

DISCHARGE 

INLET 

1. Slip the draw band clamps over each end of the duct. 

2. Slip the inlet end of the valve into the duct far enough to allow the valve 
to be lifted into the duct opening. 

3. Slip the discharge end of the 
valve into the duct engaging valve 

into duct 1” at each end.

 

 4. Position valve to provide 
unobstructed access to the 
transmitter, actuator and 
access panel. 

6. Secure both ends of valve to the duct using draw band clamps. 
 

2. Slip the discharge end of the 
valve into the duct engaging 

valve into duct 1” at each end.

 

 

1. Slip the inlet end of valve into the duct far enough to allow the valve to be lifted 
into the duct opening. 
 

4. Apply duct sealant and secure valve to duct at both ends using tek-screws. 

3. Position valve to provide 
unobstructed access to the 
transmitter, actuator and 
access panel. 

DISCHARGE 

INLET 

5. For clean air applications, 
apply UL181 compliant foil tape 
over the valve/duct seams. 

For corrosive exhaust applications, apply PTFE tape (available from Accutrol) 
over the valve/duct seams. 

4. Secure valve to duct using appropriate hardware. 
    Reference the Accutrol Vanstone Flange Detail Drawing. 

2. Position valve to provide 
unobstructed access to the 
control module, actuator 
and access panel. 

3. Install gaskets and/or 
duct sealant between 
the valve flanges and 
companion flanges. 

1. Slip the companion flanges over each end of the duct and install to duct as required. 

Summary of Contents for AccuValve AVT6000

Page 1: ...of this Manual are Subject to Change Without Notification Airflow Control Valve Patented U S 6 991 177 7 543 759 Manufactured by Accutrol Representative AVT6000 MANUAL REV B 2020 05 29 ECN 2627 21 Com...

Page 2: ...ainst defects or damages arising from improper installation where installation is by persons other than Manufacturer against defects in products or components not manufactured by Manufacturer or again...

Page 3: ...ii TABLE OF CONTENTS iii SECTION 1 INTRODUCTION 4 SECTION 2 SPECIFICATIONS 6 SECTION 3 PHYSICAL DIMENSIONS WEIGHTS 11 SECTION 4 INSTALLATION 12 SECTION 5 WIRING 15 SECTION 6 ACCUVALVE INSIGHT CONFIGUR...

Page 4: ...ambers it accelerates and compresses creating an ideal condition for measuring airflow velocity The vortex shedding airflow sensors provide a highly repeatable digital pulse train with a frequency tha...

Page 5: ...ectangular 48 12 h x 48 w Rectangular ACTUATOR 02 Fail Last Position 2 sec full cycle 0 10v PN 20 0008 03 Fail Last Position 2 sec full cycle 2 10v PN 20 0009 04 Fail Open Closed 2 sec full cycle 0 10...

Page 6: ...Airflows 120 ohm EOL network termination resistors are required Reference Appendix C for details Remote Display Sold Separately LCD 2 lines x 8 characters with white LED backlight Includes USB Configu...

Page 7: ...Glv Steel PFA Coated 304SS 304LSS Blades 304LSS 316LSS Glv Steel PFA Coated 304SS 304LSS Shafts 316LSS 316LSS 316LSS PFA Coated 316SS 316LSS Shaft Bearings Teflon Teflon Teflon Teflon Teflon Vortex Se...

Page 8: ...5 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 25 50 75 100 125 150 175 200 225 250 275 300 325 Valve DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 100 150 200 250 300 350 400 450...

Page 9: ...CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 300 600 900 1200 1500 1800 2100 2400 2700 Valve DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 400 800 1200 1600 2000 24...

Page 10: ...0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 800 1600 2400 3200 4000 4800 5600 6400 Valve DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 1000 2000 3000 4000 5000 6000 700...

Page 11: ...H Stainless Steel Aluminum in mm in mm in mm Lbs kg Lbs kg 06 5 88 149 22 559 10 254 13 5 9 9 4 1 08 7 88 200 24 610 13 330 16 7 3 12 5 4 10 9 88 250 24 610 15 381 20 9 1 14 6 4 12 11 88 300 27 686 1...

Page 12: ...re Also be sure to select a location that will provide a minimum clearance of 14 356mm unobstructed access to the transmitter actuator and valve access cover 3 Provide an opening in the duct section s...

Page 13: ...ansmitter actuator and access panel 6 Secure both ends of valve to the duct using draw band clamps 2 Slip the discharge end of the valve into the duct engaging valve into duct 1 at each end 1 Slip the...

Page 14: ...roperly 2 Lift valve into position to provide unobstructed access to the transmitter actuator and access panel The 36 and 48 wide valves are provided with integral mounting struts to help support the...

Page 15: ...AccuNet modules installed and the remote monitor connected For more details regarding the AccuNet reference Appendix B 24 vAC 24 vDC or Analog Input BMS Controller Signal Receiving Device Common Powe...

Page 16: ...Insight Software from https www accutrolllc com Run setup and follow the on screen instructions 6 3 AccuValve Insight Software Product Registration After the software has been installed on your comput...

Page 17: ...Power Source Switch which should always be in the Operational Position for the transmitter to function normally The Nonoperational Position is provided so the transmitter can be programmed or configu...

Page 18: ...6000 W with optional wireless Bluetooth module Note Reference Appendix B for Bluetooth Connection Details 6 4 3 Connecting to a remote monitor such as the AFM1 Airflow Monitor Windows 10 Device with B...

Page 19: ...6 5 1 Configuring USB Driver In some instances the Windows 10 machine being used to run Insight may not be equipped with the appropriate USB driver package needed to connect This is a possible occurre...

Page 20: ...e It may be necessary to restart your PC after installation of the CP2120x driver for the install to take effect 6 5 2 Accuvalve Insight Dashboard The Insight Dashboard is the primary screen for acces...

Page 21: ...full scale range of the Analog Output or it can be configured with a full scale range that is independent of the Analog Output To change the full scale range click on the gauge face 6 5 4 AccuNet Tota...

Page 22: ...nfiguring the Analog Output Example 1 shows the Signal Source set to Valve Airflow which is the most common configuration Example 2 shows the Signal Source set to AccuNet Airflow which is only availab...

Page 23: ...ion about the device such as MAC Address Serial Number Tag Number and USB Bluetooth com status Each of the menu items are described below 1 5 7 1 File Menu Items System Load From Transmitter Flash Mem...

Page 24: ...ownload all Generic Config files which save to the desktop Note PC must be connected to a transmitter for this function to operate Print Parameters Report Generates a report showing the present config...

Page 25: ...ability to filter the airflow volume reading and the analog output Measurement Airflow Measurement Opens the Airflow Measurement Window Configuration Airflow Units Opens the window required for config...

Page 26: ...ked this will display the communication data on the dashboard task bar 6 5 7 Dashboard Task Bar Provides the USB communication status device serial number device tag and BACnet MAC address at the top...

Page 27: ...The Accutrol AVT6000Transmitter product family supports a collection of BACnet visible objects which are defined in the following table Point Object Description Present Value Type Units DE Device Inst...

Page 28: ...ereas Flash memory does RAM memory is used by the transmitter to store and retrieve active values which are not retained when the power to the transmitter is lost Values stored in Flash memory are cop...

Page 29: ...e 3 8 bolt enough to allow the access door to slide forward CAUTION If the bolt is removed from the captive nut the access cover can spring open possibly causing injury 8 1 2 Using two hands squeeze t...

Page 30: ...cured to the valve using 4 2 blunt head Phillips head screws To inspect the sensors remove the access cover by removing the screws using a 2 Phillips head screw driver Put the screws aside for reinsta...

Page 31: ...del Code Actuator Identifier Actuator Description Actuator Part Number A2 AVT6xxx 02 Fail Last Position 0 10v High Speed 20 0008 A3 AVT6xxx 03 Fail Last Position 2 10v High Speed 20 0009 A4 AVT6xxx 04...

Page 32: ...Installation Operation Manual Model AVT6000 Page A2...

Page 33: ...Installation Operation Manual Model AVT6000 Page A3...

Page 34: ...Installation Operation Manual Model AVT6000 Page A4...

Page 35: ...Installation Operation Manual Model AVT6000 Page A5...

Page 36: ...tuator PN 20 0057 2 Screws PN 17 0246 8 32 x 5 16 Tools Required 10mm wrench 2 Phillips Head Screw Driver ELECTRICAL Power Supply 24 VAC 20 50 60 Hz or 24 VDC 10 Power Consumption 1 4 W nominal 4 0 W...

Page 37: ...devices objects in the area and building construction Because the AccuValve is typically installed in locations that have sheet metal duct work metal trusses ceiling grids and concrete with metal mes...

Page 38: ...t be comprised of AccuValves serving only one lab space Each network shall include no less than two and no more than twenty AccuValves The network shall be wired using Windy City Wire PN 042002 or equ...

Page 39: ...the wiring diagrams the termination resistors are installed and the analog output on the Totalizer is wired to the room controller The network diagram used for this example is shown in Figure 1 Step...

Page 40: ...unique network address to this AccuNet Module and AccuValve TAG name will be assigned as the TAG name of this AccuNet Module 3 1d Close the Insight Program Dashboard then disconnect the pc from the A...

Page 41: ...e network address to this AccuNet Module and AccuValve TAG name will be assigned as the TAG name of this AccuNet Module 3 4d If this device is the Totalizer continue to Step 4b If this device is not t...

Page 42: ...s not yet been configured the default device address of 127 will be shown The complete device list can only be viewed from the valve assigned as the totalizer valve All other devices will only show th...

Page 43: ...3 FUME HOOD 2 FUME HOOD 1 FHEV1 AVC6 AV6 AVC6 AVC6 Total Exhaust Air Flow AI AO AI Supply Ctrl Signal Supply Air Flow SAV1 GEV1 FHEV2 FHEV3 AO Gen Exhaust Ctrl Signal Lab Controller T T AV6 SAV TOTALI...

Reviews: