Accu-Steam™ G2 Gas Service Manual
16
SP8042-1911
5.3 Set RTD Probe Offset
In certain circumstances, the measurement from the RTD probe can be adjusted at the control
board, thereby adjusting when the unit will call for heat.
This process should only be performed by a qualified technician with access to a weighted
surface probe.
1. Turn unit on: depress the 1/0 key (To turn off the unit press and hold the 1/0 key for
approximately five seconds).
2. (Reference Fig 5.B) Press and hold the DOWN arrow key and the * key for about eight seconds
to enter Manager’s mode while the unit is on. In Manager’s mode, the first field displayed will
be the Parameter# 1, DEFAULT COOK TEMP. Scroll to the probe offset mode using the UP
arrow key or DOWN arrow key.
• Hand held field temperature meter that shows a higher temperature than the griddle
displayed temperature. Press the Preset 2 key to increase the offset number by the number
of degrees off. The griddle display will indicate the offset in as a positive number.
• Hand held field temperature meter that shows a lower temperature than the griddle
displayed temperature. Press the Asterisk (*) key to decrease the offset number by the
number of degrees off. The griddle display will indicate the offset in as a negative number.