41
AcuRev
1200
From 107H, we can see if the seal state is valid. When the sealing key is invalid, the
address displays open seal state. When the seal is valid the address displays (both 2 seal
keys are valid), seal state, and the corresponding content would be shield.
20FH
Sealing optional content
Bit0: TOU setting sealing or not
Other bits are reserved
1:Enable
0:Disable
Note:
The contents of the following table to play "√" address, communications, key
exception write operation will return an error code 02H. And you can not change the
corresponding content.
Seal standard content:
Address
Parameter description
Communication
Key
209H
Pulse option
√
√
20AH
Demand calculation method option
√
√
20BH
Demand calculation cycle
√
√
20CH
Demand calculation slid time
√
√
20DH
Reactive power calculation method
√
√
20EH
VAR/PF statute
√
√
20FH
Seal optional content
√
√
213H
Clear meter parameters
√
√
Energy :
Modbus address (HEX) Parameter description
Communication
Key
900H-901H
Total Real Energy
√
--
902H-903H
Total Real Energy tariff 1
√
--
904H-905H
Total Real Energy tariff 2
√
--
906H-907H
Total Real Energy tariff 3
√
--