50
A
cu
Re
v
12
00
energy tariff1,total active energy tariff2 from 17
th
slave device. The data type of energy is
dward. Each parameter takes 2 bits, and each bit takes 2 bytes. AcuRev 1200 series meters’
total real energy addresses are 900H, 901H. Total real energy tariff 1 addresses are 902H,
903H. Total real energy tariff 2 address are 904H, 905H.
Table 5-4 Query Frame of Reading Energy
Response
The slave device anwsers the master device's query. The response frame contains
slave device address, function code, data quantity and CRC check.
Table 5-5 is an example response of reading Total Real Energy (1.27kwh), Total Real
Energy tariff 2 (1.00kwh), Total Real Energy tariff 2 (0.27kwh). (when the energy data is
transmitting, real value= communication value/100).
Table 5-5 Response of Total Real Energy,Total Real Energy tariff 1,Total Real Energy tariff 2
Addr
Fun
Data start addr
HI
Data start addr
LO
Data #of regs
HI
Data #of regs
LO
CRC16
HI
CRC16
LO
11H
03H
09H
00H
00H
06H
C4H
C4H
Addr
Fun
Byte
count
Data1
HI
Data1
LO
Data 2
HI
Data2
LO
Data3
HI
Data3
LO
Data4
HI
Data4
LO
11H
03H
0CH
00H
00H
00H
7FH
00H
00H
00H
64H
Data5
hi
Data5
Lo
Data 6
hi
Data6
lo
CRC16
hi
CRC16
lo
00H
00H
00H
1BH
96H
8DH
Summary of Contents for AcuRev 1200 Series