68
A
cu
Re
v
12
00
Rate parameter error information word 1(basic parameter)
Table 5-22 Tariff parameter error information word 1
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
1
1
1
1
1
1
1
1
Weekend
Schedule
Setting
error
Holiday
setting
error
Holiday
Number
Exceeds
Season
Setting
error
Season
Setting
Schedule
Table
Exceeds
Schedule
Setting
Error
Rate no.
Tariff
Rate parameter error information word 2(time segment table parameter)
Table 5-23 Tariff parameter error information word 2
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
1
1
1
1
1
1
1
1
Schedule 8
error
Schedule 7
error
Schedule 6
error
Schedule 5
error
Schedule4
error
Schedule 3
error
Schedule 2
error
Schedule 1
error
Electrical measurementparameter area (03H:read)
Table 5-24 Electrical measurementparameter address
Modbus
address(HEX)
Parameter
description Data type
R/W
Data range
Default Model Register
number
800H-801H
Freq_rms
Float
R
45.00~65.00
2, 3, 4
2
802H-803H
U_rms
Float
R
0~400.00
2, 3, 4
2
804H-805H
I_rms
Float
R
0~80.000
2, 3, 4
2
806H-807H
P_rms
Float
R
-79.9999~79.999
2, 3, 4
2
808H-809H
Q_rms
Float
R
-79.9999~79.999
3, 4
2
80aH-80bH
S_rms
Float
R
-79.9999~79.999
3, 4
2
80cH-80dH
PF_rms
Float
R
-1.000~1.000
3, 4
2
80eH-80fH
RLC_val
Float
R
67('C'), 76('L'), 82('R')
3, 4
2
810H-811H
P_dema
Float
R
-79.9999~79.999
3, 4
2
812H-813H
Q_dema
Float
R
-79.9999~79.999
3, 4
2
814H-815H
S_dema
Float
R
-79.9999~79.999
3, 4
2
Summary of Contents for AcuRev 1200 Series
Page 1: ...User s Manual AcuRev 1200 Energy Meter...
Page 2: ......
Page 8: ...VI AcuRev 1200...
Page 32: ...24 AcuRev 1200 Choose Choose...
Page 35: ...27 AcuRev 1200 Figure 4 1 Basic setting parameters in the software...
Page 52: ...44 AcuRev 1200...
Page 86: ...78 AcuRev 1200...
Page 93: ......