38
A
cu
Re
v
12
00
4.6 Event Logging
The meter supports the event logging of important operations. Including
programming event, open meter cover event, demand clearance event, event clearance
event, meter clearance event.
Programming event: Record the programming time and programming event flag
when programming some important parameters of the meter. When one programming
event occur several times within 5 min, the meter just record the first time.
Programming flag
Programming event
01
Meter address programming event
02
RS485 communication programming event, including baud rate, check
mode.
03
Reserved
04
Reserved
05
Energy pulse programming event
06
Demand related programming event, including demand calculate
method, demand calculate period, slid time.
07
Reactive calculate method programming event
08
VAR/PF statute programming event
09
Change time programming event
100
Change energy base programming event
101
TOU parameter programming event
102
Daylight saving time programming event
103
Trend record programming event
Open meter cover event: Record the open and close event, support 3 groups of open
meter cover event.
Demand clearance event: Clear the demand record, support 3 groups of demand
clearance event.
Event clearance event: Clear the event record, support clear demand clearance event,
Summary of Contents for AcuRev 1200 Series
Page 1: ...User s Manual AcuRev 1200 Energy Meter...
Page 2: ......
Page 8: ...VI AcuRev 1200...
Page 32: ...24 AcuRev 1200 Choose Choose...
Page 35: ...27 AcuRev 1200 Figure 4 1 Basic setting parameters in the software...
Page 52: ...44 AcuRev 1200...
Page 86: ...78 AcuRev 1200...
Page 93: ......