71
AcuRev
1200
Modbus
address(HEX) Parameter description
Data
type R/W
Data range
Default Model Register
number
946H-947H
Generated Reactive
Energy
Dword
0~+99999999
3,4
2
948H-949H
Generated Reactive
Energy tariff 1
Dword
0~+99999999
3,4
2
94AH-94BH Generated Reactive
Energy tariff 2
Dword
0~+99999999
3,4
2
94CH-94DH Generated Reactive
Energy tariff 3
Dword
0~+99999999
3,4
2
94EH-94FH
Generated Reactive
Energy tariff 4
Dword
0~+99999999
3,4
2
950H-951H
Apparent Energy
Dword
0~+99999999
3,4
2
The last settlement date’s energy data
A00H-A51H Same to the current
energy data’s format
R
3,4
......
The 2
nd
last settlement date’s energy data
B00H-B51H
Same to the current
energy data’s format
R
3,4
Note 1
: Net Real Energy, Net Reactive Energy are signed words, the value range is
-999999.99~+999999.99
Note 2
: Real value = communication value/100
Maximum demand and time of occurrence(03H:read)
Table 5-26 Maximum demand and time of occurrence address
Modbus
address(HEX)
Parameter description
Data
type R/W
Data range
Default Model Register
number
Currentmaximum demand and time of occurrence data
1600H-1601H
1602H-1604H
Consumed Real power’s
total max demand and
occur time
Float
Dword
R
Xx.xxxx kw
YYMMDDhhmmss
(Second always
be 0)
3,4
2
3
Summary of Contents for AcuRev 1200 Series
Page 1: ...User s Manual AcuRev 1200 Energy Meter...
Page 2: ......
Page 8: ...VI AcuRev 1200...
Page 32: ...24 AcuRev 1200 Choose Choose...
Page 35: ...27 AcuRev 1200 Figure 4 1 Basic setting parameters in the software...
Page 52: ...44 AcuRev 1200...
Page 86: ...78 AcuRev 1200...
Page 93: ......