background image

Accu-Steam™ G2 Gas Service Manual

PAGE  22

SP8042-1609

Ignition System Testing

 

When trouble shooting ignition problems it is absolutely imperative to start off by 

taking incoming/outgoing gas pressure and to get a reading from the flame sensor. These 

three measurement are the most useful readings a technician can take when diagnosing 

AccuTemp gas equipment and are often the most neglected.

Flame Sense

The ACCU-STEAM  G2 gas griddle has a flame sensing circuit to determine if the system has proper 

combustion.  When the system is turned on gas is sent to the burner and an electronic ignition tries to ignite 

the griddle. The griddle then checks to see if flame is established in the burner. If the flame sense feedback is 

within the proper range the system will stay on until the digital temperature controller is satisfied. The griddles’ 

ignition module continues to monitor the voltage and as long as its within the proper range the griddle will stay 

on. If the flame sense reading falls below the threshold (

13mV or .32uA

) the griddle will go into lock out and 

will stop heating. When a lock out occurs, the fault indicator light should illuminate.

Micro-amp flame sense reading

A meter with micro amp (<A) selection or a micro amp adapter must be place in series with the orange flame 

sense wire. To check micro amps, disconnect the orange wire from the flame rod and connect the amp meter in 

series by attaching one lead of the meter to the flame sense rod terminal and the other lead to the orange wire. 

Millivolts flame sense reading

An Accutemp volt-measuring adapter P/N FT0003 (meter set for millivolts) is placed in parallel with the orange 

flame sense circuit. To check millivolts, attach one end of the adapter to the orange wire and the other to ground.

If the burner is lighting, determine if the sensing signal level is 30mV (1.38uA) or higher.

A. If the reading is less than 30mV (1.38uA), check for proper gas pressures to the dual valve. For natural gas, 

the pressures must be 5” water column for the main gas valve. For propane gas, the pressures must be 10” water 

column.

B. If the gas pressures are good but the sensing signal level is still poor, check burner orifice for obstruction. 

Clean or replace as necessary.

C. If the gas pressures are good, the pilot orifice is clean, the burner surface is glowing orange to bright orange 

but the signal level is still poor, clean or replace the flame sense probe.

Four types of meter readings are possible:

1)

 0 millivolts or micro amps

 – Look for an open or grounded sensor wire or flame rod,

or a defective ignition module. The wire and rod can be diagnosed with an ohmmeter. 

2)

 Steady 30 DC millivolts or 1.38 micro amps or higher

 – The system is operating within normal parameters.

3) 

Fluctuating meter reading

 – Check that the flame sensor probes are properly located. Also check for drafts 

that can cause an unstable flame. A dirty orifice can also cause an unstable flame.

4) 

Less than 30 millivolts or 1.38 micro amps 

– Verify the flame-sensing rod is properly engulfed in the flame. 

A flame sensor probe too close to the tile will not be in the proper part of the flame, with not enough ionized gas 

to allow a proper signal level to be conducted. Conversely, the same thing holds true if the flame sensor

is too high. Also check the ground connection back to the ignition module. Check that the flame-sensing rod and 

ground plane are not oxidized. Clean both with a non aluminum oxide abrasive.

Summary of Contents for G2

Page 1: ...d result in property damage serious injury or death Read and understand the installation operational maintenance instructions before installing servicing or operating this commercial appliance Serial...

Page 2: ...Accu Steam G2 Gas Service Manual PAGE 2 SP8042 1609 Toll Free 800 480 0415 Office 260 469 3040 Fax 260 493 8914 Email service accutemp net Web Site www accutemp net...

Page 3: ...an imminently hazardous situation which if unchanged will result in death or serious injury DANGER Indicates a potentially hazardous situation which if unchanged will result in minor or moderate inju...

Page 4: ...GIZED EQUIPMENT Unplug equipment prior to removing any components effected by electricity PERSONNEL INJURY HAZARD WHILE PICKING UP OR MOVING HEAVY EQUIPMENT Always use at least 2 people and proper lif...

Page 5: ...ation and service maintenance instructions thoroughly before installing or servicing this equipment WARNING Only QUALIFIED service technicians electricians should perform the equipment installation to...

Page 6: ...Accu Steam G2 Gas Service Manual PAGE 6 SP8042 1609 WARNING CAUTION NOTES ONLY QUALIFIED SERVICE TECHNICIANS SHOULD PERFORM MAINTENANCE ON THIS EQUIPMENT WARNING CAUTION GRIDDLE MAY HAVE SHARP EDGES...

Page 7: ...rts Identification Removal and Installation Fuses Control Relay Control Board Hi_Limit Control Board Transformer Heat Lamp Fault Timer Gas Valve Ignition Control Module Flame Sensor Igniter Infrared B...

Page 8: ...relay in the Hi Limit controller will be opened causing the 24VAC to be cut off from the ignition control DC relay and to the pilot valve coil of the gas combination valve closing the pilot valve 9 Th...

Page 9: ...o see a sufficiently high enough DC voltage level through the flame sense circuit the ignition module will disable 24VAC from the red harness and the timer will see the voltage potential from the chas...

Page 10: ...ERNAL VOLTAGE A B C NO NO BREAKER ON UNIT PLUGGED IN YES YES NO NO FAULT LIGHT ERROR CODE D E OVERTEMP YES HEAT ON H I NO UNIT HEATING UP HEAT LIGHT ON YES NO NO ERROR CODE E001 E002 PROPER TEMPERATUR...

Page 11: ...nput to transformer is present and there is no output replace transformer D Error Code E001 or E002 on display E001 Open Temp RTD sensor J3 1 J3 2 Check terminals for poor crimping E002 Shorted Temp R...

Page 12: ...e relay I Unit not heat ing up Check for 24 VAC to the gas valve If no voltage to the gas valve check for poor or loose connections or broken red wire between the heat lamp and the gas valve If there...

Page 13: ...Lock Unlocked Note If temperature is unable to be adjusted user may need to unlock the system by holding down the ON OFF S5 button and Temp S6 button together for 8 seconds or until ULOC is displayed...

Page 14: ...for five seconds will reset the soft ware back to the factory default settings Error Codes The control will display error codes for the following conditions E001 Displays when controller detects an O...

Page 15: ...opens and supplies gas to the burners when the control board calls for heat Ignition Control Module AT2E 1807 1 Takes reading from the flame sensor Receives input from temperature Controller and Hi Li...

Page 16: ...e panel 3 Replace fuse Hi Limit RTD Temp Sensor RTD Igniter Fuse Block Transformer Fault Timer Hi Limit Control board Ignition Control Module Main Control Board Control Relay Control Valves Tap Contro...

Page 17: ...nuts and washers securing board to panel remove panel 5 Reinstall in reverse order Hi Limit Control Board AT0E 3880 1 1 Unplug from wall receptacle 2 Lower front access panel by removing the screws i...

Page 18: ...r 1 Unplug from wall receptacle 2 Lower front access panel by removing the screws in the upper corners of the panel 3 Locate transformer and note the location of the wires and their terminals disconne...

Page 19: ...remove wires 4 Remove hardware securing module 5 Remove module 6 Reinstall in reverse order 1 Unplug from wall receptacle 2 Turn off gas supply and disconnect the unit from supply hose 3 Lower front a...

Page 20: ...tacle 2 Lower front access panel by removing the screws in the upper corners of the panel 3 Remove igniter wire 4 Remove screws and igniter 5 Reinstall in reverse order 6 Set new igniter gap between 1...

Page 21: ...the upper corners of the panel 3 Locate and remove RTD wires attached to the Hi Limit control Board 4 Remove nut securing RTD to griddle 5 Reinstall in reverse order RTD Resistance Chart RTD Testing...

Page 22: ...laced in parallel with the orange flame sense circuit To check millivolts attach one end of the adapter to the orange wire and the other to ground If the burner is lighting determine if the sensing si...

Page 23: ...w the appliance to heat up to at least 200 F First check the main burner regulator pressure Remove the rubber hose and replace with the manometer tube The pressure should be 5 WC for natural gas and 1...

Page 24: ...rush and or emery cloth Caution DO NOT use any abrasive that contains aluminum oxide This will leave a coating on the flame sensor that could cause the unit not to light X X Clean all gas orifices mak...

Page 25: ...WHT BLK RED YEL BLU HEAT RED RED BLK WHT 240V 208V 120V COM 24V RED ORN 75 A F2 75 A F1 IGN FAULT BLU WHT FAULT TIMER 1 2 3 1 2 J2 POWER INPUT DIGITAL CONTROLLER ON OFF 1 2 3 4 5 6 J7 24V GND 1 2 J3 S...

Page 26: ...eceived advance approval from AccuTemp factory service to perform the repair or replacement This warranty includes travel time not to exceed two hours and mileage not to exceed 50 miles 100 miles roun...

Page 27: ...________________ ____________________________________________ ____________________________________________ ____________________________________________ ____________________________________________ ___...

Reviews: