Accu-Steam™ G2 Gas Service Manual
PAGE 14
SP8042-1609
Digital Controller
Operating Mode
When power is applied to the control, the control will configure itself to operate in accordance with the parame
-
ters stored in memory. These parameters may be adjusted using Manager’s Mode.
Reset
Pressing and holding the
DOWN
(S4) arrow key and the
ON/OFF
(S5) key for five seconds will reset the soft
-
ware back to the factory default settings.
Error Codes
The control will display error codes for the following conditions:
E001 Displays when controller detects an Open Sensor
E002 Displays when controller detects a Shorted Sensor
9999 No calibration data stored or invalid calibration data detected
To reset from any error, unit must be turned OFF, repaired, and then turned ON.
When any error is displayed, outputs are forced open. The following chart illustrates the programming logic and
program level indication: