6
E) Checking the tightness of the refrigeration lines (Fig. A)
1) Open the caps of the sectioning valves (Fig. A n. 1).
2) Check that the section valves are closed (Fig. A n. 2).
3) Remove the plug from the service connection on the valve
sectioning (Fig. A n. 3).
4) Connect the pressure gauge and the nitrogen bottle to the
valve stop then gradually increase the pressure in the pipes
of the refrigerant connection and in the internal module at 35
bar, in 5 bar increments (Fig. A n. 4).
5) Check the tightness of the fittings with a detector spray
escapes. If there are leaks, repeat the operations in the order
indicated and check the seal again (Fig. A n. 5).
6) Leave the circuit under nitrogen pressure for at least 24 hours e
check that at the end of this time the pressure initial does not go down.
7) Release the pressure and nitrogen.
.
Fig. A
1
3
35 bar
4
2
ATTENZIONE!
2
ATTENZIONE!
5
1
Gas side cock
Liquid side tap
(Example A) INSTALLATION WITHIN 5 METERS
Example of installation without additional gas refill R410a
refrigerant, distance 4 meters.
2 m
0,5 m
1,5 m
Example A
of table 4
(B) INSTALLAZIONE CON LUNGHEZZA MINIMA AMMISSIBILE
Qualora la distanza tra le unità Unità Interna ed Unità Esterna sia
inferiore a 3 metri (come in questo caso dove la lunghezza delle
tubazioni non superano i 2 metri), bisogna tagliare le tubazioni a
3 metri ed arrotolare la parte finale in corrispondenza dell’ l’unità
esterna.
Spirale lung. 1 metro
0,5 m
1,5 m
Esempio B
della tabella 4
(C) LUNGHEZZA MASSIMA TUBAZIONE
(D) DISLIVELLO MASSIMO AMMISSIBILE (tra U.E e U.I.)
(E) QUANTITÀ REFRIGERANTE ADDIZZIONALE (oltre i 5 m)
In questa configurazione la lunghezza effettiva delle tubazioni è
di 6 m in orizzontale e di 4 m in verticale, in totale 10 m.
Andremo quindi ad aggiungere 100 grammi di di gas refrigerante
di R410a ovvero 5 m x 20 g/m = 100 grammi.
Esempio C - D - E
della tabella 4
4 m
6 m
HR 3.0
5*m
3*m
15*m
5*m
20*g/m
HR 7.8
5*m
3*m
15*m
5*m
20*g/m
Models
A
Maximum length allowed without adding refrigerant
B
Minimum allowed length of refrigerant gas
C
Maximum length of refrigerant gas piping
D
Maximum admissible height difference between U.E and U.I.
E
Additional refrigerant quantity over 5 meters
Table 4 - Admissible distances U.I. - E.U.
Failure to comply with this application
will result in the non-ignition by the authorized assistance
Summary of Contents for HUB RADIATOR MINI 11.0
Page 27: ...27 7 2 WIRING DIAGRAM HUB RADIATOR MINI XL 6 0...
Page 28: ...28 7 3 WIRING DIAGRAM HUB RADIATOR MINI XL 8 0...
Page 29: ...29 7 4 WIRING DIAGRAM HUB RADIATOR MINI XL 11 0...
Page 30: ...30 7 5 WIRING DIAGRAM HUB RADIATOR MINI XL 16 0...
Page 31: ...31 Marrone Nero Blu 7 6 WIRING DIAGRAM HUB RADIATOR MINI XL 24 0...
Page 46: ...46...