19
in the group.
The lower display shows the parameter label and the upper
display shows the value.
5.5 VIEW AND MODIFY THE SET POINT
Pressing and releasing the
SET
key allows the set point to be
displayed.
Pressing the
SET
key for a long time allows its modification:
1 Press the
SET
button for at least 3 seconds;
2 The set point will be displayed flashing;
3 To modify the value, use the keys
And
4 Save the new set point by pressing the
SET
or button
wait for the time out time to exit the program.
User interface
Remote terminal
5.6 MAIN ALARMS
Cod.
Meaning
It causes
Action
Reset
P1
Probe alarm
Probe faulty our
Activate output open
Automatic
PB1
resistive value
collector / relè alarm
if the value is within
out of range
Activate buzzer
the expected range
Flashing icon
generic alarm
Code on display
P2
Probe alarm
Probe faulty our
Activate output open
Automatic
PB2
resistive value
collector / relè alarm
if the value is within
out of range
Activate buzzer
the expected range
Flashing icon
generic alarm
Code on display
P3
Probe alarm
Probe faulty our
Activate output open
Automatic
PB3
resistive value
collector / relè alarm
if the value is within
out of range
Activate buzzer
the expected range
Flashing icon
generic alarm
Code on display
P4
Probe alarm
Probe faulty our
Activate output open
Automatic
PB4
resistive value
collector / relè alarm
if the value is within
out of range
Activate buzzer
the expected range
Flashing icon
generic alarm
Code on display
A12
Defrost
End defrost for
Code on display
Automatic
error alarm
maximum time
reporting only
with subsequent
correct defrost
cycle
A09
Compressor
Condensation start
Activate output open
Automatic
thermal alarm
temperature
collector / relè alarm
with subsequent
of 110 °C
defrost icon flashing
correct defrost
Generic alarm
cycle
Code on display
ALOC
Low or high voltage
Power supply voltage
Activate output open
Automatic
alarm or higher
below 220V
collector / relè alarm
it becomes manual after
than 256V
activates Buzzer
defrost icon flashing
AL20 interventions now
Generic alarm
Manual
Code on display
Deactivation: digital
input not active for
continuous time >AL22
E01
Refrigerant circuit
Refrigerant circuit
Activate output open
Manual
high pressure
pressure higher
collector / flashing
alarm
than 42 bar
generic alarm icon
E02
Refrigerant circuit
Refrigerant circuit
Activate output open
Manual
high pressure
pressure below
collector / flashing
alarm
2,7 bar
generic alarm icon
pressione circuito
frigorifero
collector / Lampeggio
frigorifero
inferiore a 2,7 bar
icona allarme generico
Summary of Contents for HUB RADIATOR MINI 11.0
Page 27: ...27 7 2 WIRING DIAGRAM HUB RADIATOR MINI XL 6 0...
Page 28: ...28 7 3 WIRING DIAGRAM HUB RADIATOR MINI XL 8 0...
Page 29: ...29 7 4 WIRING DIAGRAM HUB RADIATOR MINI XL 11 0...
Page 30: ...30 7 5 WIRING DIAGRAM HUB RADIATOR MINI XL 16 0...
Page 31: ...31 Marrone Nero Blu 7 6 WIRING DIAGRAM HUB RADIATOR MINI XL 24 0...
Page 46: ...46...