49
UK
1
Omit Al+Tamp
You can block some zones and tamper
zones or a tamper alarm from
monitoring.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
053 Cancel - Reset
To change the property of the alarm reset:
1. On the control unit, enter:
053
2. The LCD display shows: 053:Abort=System
3. Via the keypad, select from the following items
and press:
0
Abort=System
Resetting after a cancelled alarm is as
set in function 33.
1
Abort=User
The user may make a reset after a
cancelled alarm.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
060 Entry/exit behaviour on internal active
(B)
To change the zone property of the entry/exit zone at
internal active (B):
1. On the control unit, enter:
060
2. The LCD display shows: 060: B=FE =FE
3. Via the keypad, select from the following items
and press:
0
B=FE =FE
A zone programmed as entry/exit keeps
this property even for internal activation
and thus starts the entry delay time
when the zone triggers and during
active internal activation.
1
B=FE = NA
A zone programmed as entry/exit
changes its zone property during
internal activation to immediate and
triggers an alarm if the zone triggers
and during active internal activation.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
061 Entry to follow behaviour on internal
active (B)
To change the zone property for internal active (B):
1. On the control unit, enter:
061
2. The LCD display shows: 061: B=ER =ER
3. Via the keypad, select from the following items
and press:
0
B=ER =ER
A zone programmed as entry to follow
keeps this property even during internal
activation and permits entry to this zone
during the entry delay period.
1
B=ER = FE
A zone programmed as entry to follow
changes its zone property during
internal activation to entry/exit and
starts the delay time if the zone triggers
and during active internal activation.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
Summary of Contents for Terxon SX AZ4000
Page 10: ...10 D 8 bersicht der Geh usekomponenten 1 2 3 4 6 5 7 8...
Page 76: ...76 D...
Page 86: ...10 UK 8 Overview of housing components 1 2 3 4 6 5 7 8...
Page 148: ...4 FR 16 Fiche technique 72 17 D pannage 73 18 Index 74 19 Plan du syst me 75...
Page 154: ...10 FR 8 Vue d ensemble des composants du bo tier 1 2 3 5 7 8 4...
Page 220: ...76 FR...
Page 230: ...10 NL 8 Overzicht van de componenten van het huis NL 1 2 3 4 6 5 7 8...
Page 294: ...74 NL...