23
o
Ethernet UDP or TCP. The choice of UDP or TCP should
match the setting of the monitoring station receiver.
o
GPRS UDP or TCP. The choice of UDP or TCP should match
the setting of the monitoring station receiver.
Target type: transmission method. Currently only IP address is
possible.
Address: IP address of the monitoring station receiver.
Port: port number of the monitoring station receiver. The
monitoring station often differentiates between the primary path
and redundant path using the port numbers.
Direction: set to 'Outgoing'.
Alarm protocol:
o
SIA DC3, first generation SIA IP transmission. DC3 and UDP
can only be combined if there is a fixed IP address for the
premises.
o
SIA DC9, second generation SIA IP transmission including
text.
o
SIA DC9 Encrypt: the DC9 notification is encrypted via AES.
The encryption method can be set in the 'Encryption' tab.
The encryption should also be set on the monitoring station
receiver in order to ensure problem-free receipt of the data.
o
SIA DC-09 A.ASCII: SIA DC-09 variant, compatible with
receivers from Azur (Osiris) and ESI (F1). These are mostly
used in France and Belgium.
o
SIA DC-09 A.Encrypt: SIA DC-09 variant with encryption
compatible with receivers from Azur (Osiris) and ESI (F1).
These are mostly used in France and Belgium. The
encryption method can be set in the 'Encryption' tab. The
encryption should also be set on the monitoring station
receiver in order to ensure problem-free receipt of the data.
o
CID DC-09: second generation IP transmission in Contact ID
DC-09 structure.
o
CID DC9 Encrypt: second generation IP transmission with
encryption in Contact ID DC-09 structure. The encryption
method can be set in the 'Encryption' tab. The encryption
should also be set on the monitoring station receiver in order
to ensure problem-free receipt of the data.
o
VdS 2465 needs-based: IP transmission in VdS 2465
structure including text as needs-based connection.
o
VdS 2465 needs-based encrypt.: IP transmission in
VdS 2465 structure including text with encryption as needs-
based connection. The VdS 2465 notification is given an
AES 128 key and key number when sent. The key and key
number should also be set on the monitoring station receiver
in order to ensure problem-free receipt of the data.
ID no.: the identification number for the notification to the
monitoring station must have no less than four and no more than
eight digits. Set the same ID number in the alarm system.