Signal lines
The motherboard is equipped with eight monitored lines (inputs). These inputs
can be adjusted per line and used as NO (normally open) or NC (normally
closed) contacts. They are monitored with a resistance of 10 K or with two
resistances of 8 K2/15 K (8 K2 idle, 23 K2 when there is an alarm; zero and
open lead to tampering/fault). Separate settings are provided for connection to
Siemens or Bosch fire alarm systems.
Plugs:
L1 C L2 L3 C L4 L5 C L6 L7 C L8
Lx = monitored line (zone)
C = common
D1 = digital line (zone) 1
C = common
D2 = digital line (zone) 2
Outputs
The two relay outputs are marked with OUT1 and OUT2.
OUT1 NO
transmission error if an alarm notification is not accepted within
three attempts
OUT2 NC
fault with LAN, GPRS communication, supply, start (booting)
OUT1 is active when there is a transmission error. The reset occurs after a
notification is acknowledged. OUT2 can be configured for each connection path.
USB
The USB port has a 5-pin USB mini connection, which is used for programming,
firmware updates and diagnostics.
Converter connection (POTS)
The PSTN converter with the RJ11 port provides the option of connecting an
analogue alarm system with SIA, Contact ID or Telim. The converter is supplied
with a line voltage of 40 V for the dialling tone, Telim, SIA and Contact ID as
well as for evaluation and conversion to VdS 2465 IP or DC-09 IP transmission
protocols. The telephone number and ID number must be set in the alarm
system; see chapter 'Param-It+ programming'.
SIM card
The SIM card must support GPRS (2G) IP data transmission. For redundant use,
1 MB per month is sufficient. The AZWG10200-PSTN/IP CONVERTER supports
multi-roaming SIM cards.