Installation –
Installation site requirements |
13
Installation
It is recommended to have the entire installation of the wallbox carried out by a qualified specialist electrical con-
tractor.
DANGER!
Dangerous electrical currents
Electrical installation, as well as final testing and certification for operation must be carried out by a qualified
specialist electrical contractor, who, on the basis of their specialist training and experience, as well as their
knowledge of the relevant standards, is able to assess and carry out the working steps described in this manual
and recognise potential hazards.
Installation site requirements
Your wallbox is suitable for outdoor use. Please note, however, that the permissible ambient conditions (see "Technical
The installation site must be freely accessible.
The mounting surface must be level and solid.
The mounting surface must measure at least 437 × 328 mm
(height x width).
328 mm
437 mm
The installation height should be between 120 and 140 cm
(ground to bottom edge of housing).
120 ~ 140 cm
Minimum distances to other technical installations must be
observed. A minimum distance of 50 cm is recommended.