4. System requirements/limitations
• Only one
SBC
home
per main fuse
• Minimum 6A must be available per charge point. Single-phase charging with six charge
points requires:
› minimum three-phase 16A for TN network
› minimum three-phase 25A for IT network
• Maximum main inlet fuse size: 4x63A (TN) or 3x80A (IT)
•
SBC
home safety margin for the system in total is 10%
• Maximum 6 charge points for three-phase charging
• Maximum 2 charge points for single-phase charging
• Maximum 5 charge points for three-phase charging for IT network with local TN network
via a 25kVA transformer
• Compliant with charge controllers from ABL with firmware 2.7C/CD, 2.8C/CD or newer
• Use Mode-3 cable only. Mode changing adaptors between charge point and vehicle are
not allowed according to international standardization
•
SBC
home
is not compliant with Mode-1 or Mode-2 charging
• eMH3 with RFID reader is not compatible with
SBC
home