Factory default settings:
• Power line in: TN network
• Main inlet fuse size: 6A
• Total charging current: 6A
• Number of charge points: 1
• Charge point: single-phase
16.
Configuring
SBC
home
Instructions for downloading the software to configure
SBC
home are described on a separate sheet in the
SBC
home
package.
Note! Configure according to the "power line in" network.
• Connect a Windows computer or an Android device to the
SBC
home's communication port. Use the USB-RS485
interface from
ABL
to connect a PC. Use an additional USB
adapter cable to connect to an Android device.
• Configure
SBC
home according to your installation.
›
Warning! If
SBC
home is configured incorrectly, the
main fuse can trip or charging performance may be
decreased.
• After configuring
SBC
home, close the communication and
disconnect the PC/Android device.
• Connect the communication cable from the wallbox(es) to
SBC
home's communication port.
Important: To start up
SBC
homeCLU with the new
configuration, disconnect power from
SBC
homeCLU and
wait for 10 seconds before powering it up again.