47
1
Environmental
Value
Environments category
E
EMC environment
Environment A
Operating temperature (without derating)
-20 - +40 °C
Operating temperature (with derating)
-25 - +70 °C
Transportation and storage temperature
-40 - +70 °C
Altitude (without derating)
Up to 2000 m
—
Table 7.2 General technical data of automatic transfer switch
Type
Voltage
[Vac]
Nominal
current*
[A]
Operating
transfer time
1, 2
AUTO mode
I-II or II-I
[ms]
Contact
transfer
time
1
I-II or II-I
[ms]
ZTX 30 - 260A
200 - 480
37
< 500
< 50
ZTX 400 - 600A
200 - 480
40
< 500
< 50
ZTX 800 - 1200A
200 - 480
40
< 500
< 50
1
Under nominal conditions
2
Time from source fail detection to contact closing on already-available secondary source
3
All times consider that all timers are set to "0"
—
Table 7.3 Specified technical data of operating times
Recommended Operating / Storage Temperature
Do not store the automatic transfer switch in corrosive environments above LC1 (sea
salt mist) and G1 as per ANSI/ ISA-S71.04-1985. Failure to comply with these instruc-
tions may result in product damage. Store the automatic transfer switch and related
accessories in a clean, dry location in their original packaging.
Summary of Contents for Zenith ZTX Series
Page 2: ...2 ...
Page 6: ...6 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Page 10: ...10 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Page 34: ...34 1 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 50: ...50 1 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE Figure A Figure B ...
Page 51: ...51 1 Figure C ...
Page 52: ...52 1 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 54: ...2 54 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 66: ...2 66 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 70: ...2 70 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...