Ze nit h Z T X se r i e s AT S , O PER ATI O N , M A I NTEN A N CE , A N D I N S TA LL ATI O N G U I D E
Alarm condition
Fault
Action
S1 invalid frequency
Frequency of source 1 is out of range
set in parameters “Drop-out frequency,
upper threshold“ and “Drop-out
frequency, lower threshold“
Check the correlation between power
source and device configuration
S2 undervoltage
Voltage of source 2 is under the
threshold level set in parameter
“Dropout voltage, lower threshold“
Check the correlation between power
source and device configuration
S2 overvoltage
Voltage of source 2 is over the
threshold level set in parameter
“Dropout voltage, upper threshold“
Check the correlation between power
source and device configuration
S2 phase missing
One or two phases of
source 2 are missing
Check the power source
and connections
S2 unbalance
Phases of source 2 are not symmetric
Check the power source
S2 phase rotation
Phase rotation of source 2 is
different from the value of
parameter “Phase sequence“
Connect the phases according
to the configuration
Frequency Difference
Frequency difference of voltage
sources is greater than 3 Hz while
inphase monitor is on
Alarm is active and transfer operations
disabled as long as the frequency
difference is above the accepted level
S2 invalid frequency
Frequency of source 2 is out of range
set in parameters “Drop-out frequency,
upper threshold“ and “Drop-out
frequency, lower threshold“
Check the correlation between power
source and device configuration
Open I failure, Alarm
LED blinking
Switch transfer from
position I to O or II failed
Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Close I failure, Alarm
LED blinking
Switch transfer to position I failed
Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Open II failure, Alarm
LED blinking
Switch transfer from
position II to O or I failed
Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Close II failure, Alarm
LED blinking
Switch transfer to position II failed
Reset alarm by pressing Auto button or
via menu page Operation / Alarm Reset
Switch position alarm,
Alarm LED on
More than one switch position
indication inputs are activated
Switch service needed, contact ABB
Local bus
Communication between HMI
and switch controller is off
Check connection
Control Voltage
Failure
Control voltage dropped
during switch control
Check power source
Control Voltage Low
Switch control voltage is
below the minimum
Check power source
Configuration Error
Invalid configuration
Check parameter values
Table 6.1 Alarms-list in ZTX via Ekip Connect
Summary of Contents for Zenith ZTX Series
Page 2: ...2 ...
Page 6: ...6 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Page 10: ...10 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Page 34: ...34 1 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 50: ...50 1 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE Figure A Figure B ...
Page 51: ...51 1 Figure C ...
Page 52: ...52 1 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 54: ...2 54 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 66: ...2 66 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 70: ...2 70 Zenith ZTX Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...