5 - Installation
The settings are made by using the keypad and the display on the meter:
1. Press for two seconds to access the setup menu of the meter.
2. Press repeatedly
until the display shows “
Set
”.
- Press
to confirm.
3. Press repeatedly
until the display shows “
RS-485
”.
- Press
to confirm.
4. Press repeatedly
until the display shows “
Prot
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly
until the display shows “
Modbus
”.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
5. Press repeatedly
until the display shows “
Baud
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select 19200.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
6. Press repeatedly
until the display shows “
Address
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select 1.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
7. Press repeatedly
until the display shows “
Parity
”.
- Press to access.
- Press to enable the change in the value.
- Press repeatedly and select even.
- Press
to confirm the change.