APPAR ATUS CO NTRO L TESTING
INTERLOCKS BETWEEN PANELS
1VLG5000 17 C
55
Step 5/10
On the protection relay LHMI (upstream circuit breaker) go to ->
Main Menu/Monitoring/
I/O status/Current protection/PHIPTOC1/Inputs
–
BLOCK = True
Figure 83: Activating blocking mode
Step 6/10
On the protection relay LHMI (tested feeder) go to->
Main Menu/Test/Function tests/
Current protection
–
PHIPTOC1 = Deactivate START
Figure 84: Deactivating START signal