ETHER NET NETWOR K VER IFICATIO N
MANAGED ETHER NET SWITCHES
1VLG5000 17 C
7
3.2
Managed Ethernet switches
To create a reliable Ethernet network for IEC 61850 communication, a managed Ethernet
switch is recommended to be used. The most important settings of ABB’s AFS family Ether-
net switches to be observed are highlighted in this section.
AFS Family
If the IP address is unknown, disconnect all Ethernet cables from the switch or turn other
Ethernet switches off. After connecting a notebook with the AFS Finder SW tool to any port
on the Ethernet switch, the following dialogue screen appears (shown in Figure 8). AFS Finder
automatically searches the network for those devices, which support the AFS finder protocol.
The next dialogue, open by double clicking on the respective switch in AFS finder defines the
IP address and net mask.
Figure 8: Properties dialogue of discovered Ethernet switch by AFS Finder
The user-friendly web-based interface of AFS switches offers the possibility of operating the
device from any location in the network via a standard browser such as Mozilla Firefox or Mi-
crosoft Internet Explorer. Being a universal access tool, the web browser uses an applet which
communicates with the device via the Simple Network Management Protocol (SNMP). The
Web-based interface allows the device to be graphically configured.
Login
Default User name to configure the AFS67x family is
admin
and the password is
admin
.
Default User name to configure the AFS66x family is
admin
and password is
abbadmin
.
Figure 9: Login window
Summary of Contents for UniGear Digital
Page 1: ...DISTRIBUTION SOLUTIONS UniGear Family UniGear Digital Commissioning and testing Guide...
Page 2: ......
Page 3: ...DISTRIBUTION SOLUTIONS UniGear Family UniGear Digital Commissioning and testing Guide...
Page 6: ......
Page 10: ......
Page 12: ......
Page 96: ......
Page 98: ...Visit us www abb com mediumvoltage Document Number 1VLG500017 Rev C...