- 150 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
FieldBusPlug / Issue: 03.2012
VI150 and VI155
General
Mounting
Snap-on mounting onto 35 mm standard mount-
ing rails
Mounting position
Any.
A distance of 10 mm left and right to the
L1 and L3 terminals might be necessary depend-
ing on the other devices mounted beside for
voltages > 230 V / 400 V respectively.
Dimensions (W x H x D)
22.5 x 77 x 100 mm
(excluding communication connector)
LEDs: Red/yellow/green
Red: Error of module
Yellow: Diagnosis available
Green: Ready for operation
Supply voltage
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Supply current (relay activated)
VI150: Max. 40 mA (at 19.2 ... 31.2 V DC)
VI155: Max. 55 mA (at 19.2 ... 31.2 V DC)
Tightening torque for the input, output and supply
terminals
See DX1xx module
Tightening torque for the communication terminals
See DX1xx module
Net weight
0.11 kg
Degree of protection
IP20
Temperature range
storage -25 ... +70 °C
operation 0 ... +60 °C
Marks, Approvals
CE, cUL
Furher in preparation. Ask your local sales repre-
sentative for other marks/approvals.
Operation altitude above sea level
VI150: max. 2000 m
VI155: max. 2000 m at 60 °C
For higher altitudes please contact your sales unit.
Relay Outputs
Number of relay outputs
1
DO0 with root DOC
Voltage range of contacts
12-250 V AC/DC
U
imp
U
imp
=4 kV
Other technical data for the relay outputs see the DX1xx module