TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
53
TZIDC-210, TZIDC-220 error codes
Error code
Possible cause
Impact
Troubleshooting the Instrument
Defective memory chip
Device does not boot up.
Return the device for repair.
Automatic adjustment function lasts too long.
Automatic adjustment function is
aborted.
.
Increase the supply pressure or use
boosters.
Mounting conditions not correct. Position outside
sensor range.
Autoadjust function is aborted.
Check mounting conditions.
1 Inconsistent data, e.g., low value > than high value,
or incorrect configuration.
2 Data cannot be saved locally, as PROFIBUS saves
data in the background.
1 Automatic adjustment is aborted.
2 Saving is not possible.
1 Correct values or load factory
settings.
2 Try again at a later point.
The device is not in the safe position.
Move the device to the safe position.
Alarm message (can only be read out using the DTM).
• Temperature
alarm
• Automatic adjustment has failed
• Zero point has shifted
• Device
reset
• Maintenance
required
• Motion counter limit value up-scaled
• Travel counter limit value up-scaled
• Limit switch 1 up-scaled
• Limit switch 2 up-scaled
• Position outside operating range
• Position outside sensor range
• Invalid set point
• Local operating mode requested
• Local operating mode active
• Simulation
active
• Controller
deactivated
See DTM online help
See DTM online help
No PROFIBUS communication.
No PROFIBUS communication.
Check bus address and status bit (128).
Position sensor defective
Device moves to safety position.
Return the device for repair.
Defective memory chip
Device does not boot up.
Return the device for repair.