46
TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
… 10 Operation
… HART® Parameter Overview
Parameter Display
Function
Possible
parameter setting
Unit
Factory setting
P6._
MAN_ADJ
P6.0
MIN_VR
Min. valve range
Operating range, min.
0.0 to 100.0
%
0
P6.1
MAX_VR
Max. valve range
Operating range, max.
0.0 to 100.0
%
100
P6.2
ACTUATOR
Actuator type
Actuator type
LINEAR, ROTARY
---
LINEAR
P6.3
SPRNG_Y2
Spring action (Y2)
Spring action (Y2) CLOCKWISE,
CTCLOCKWISE
---
CTCLOCKWISE
P6.4
DANG_DN
Dead angle close
Dead angle 0 %
0.0 to 45.0
%
0.0
P6.5
DANG_UP
Dead angle open
Dead angle 100%
55.0 to 100.0
%
100.0
P6.6
BOLT_POS
Bolt position
Actuator position
LEVER, STEM
---
LEVER
P6.7
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P7._
CTRL_PAR
P7.0
KP UP
KP value, up
KP value (up)
0.1 to 120.0
---
5.0
P7.1
KP DN
KP value, down
KP value (down)
0.1 to 120.0
---
5.0
P7.2
TV UP
TV value, up
TV value (up)
10 to 450
---
200
P7.3
TV DN
TV value, down
TV value (down)
10 to 450
---
200
P7.4
Y-OFS UP
Y offset, up
Y offset (up)
0.0 to 100.0
%
48.0
P7.5
Y-OFS DN
Y offset, down
Y offset (down)
0.0 to 100.0
%
48.0
P7.6
TOL_BAND
Tolerance band (zone) Tolerance band (zone)
0.3 to 10.0
%
1.5
P7.7
DEADBAND
Deadband
Dead band
0.10 to 10.00
%
12:10 AM
P7.8
DB_APPR
Deadband Approach
Dead-band approach
SLOW, MEDIUM, FAST
P7.9
TEST
Test
Test
Function
---
INACTIVE
P7.10
DB_CALC
Deadband calculat.
Dead-band determination
ON, OFF
---
ON
P7.11
LEAK_SEN
Leakage sensivity
Leakage sensitivity
1 to 7200
S
30
P7.12
CLOSE_UP
Pos. time out
Position monitoring
0.0 to 100.0
%
30.0
P7.13
EXIT
Return
Return to operating level
Function
---
NV_SAVE