TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
45
Parameter descriptions
Parameter Display
Function
Possible
parameter setting
Unit
Factory setting
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
Actuator type
LINEAR, ROTARY
---
LINEAR
P1.1
AUTO_ADJ
Automatic
adjustment
Autoadjust
Function
---
---
P1.2
ADJ_MODE
Auto adjust mode
Automatic adjustment mode
FULL,STROKE,CTRL_PAR, ZERO_POS, LOCKED
FULL
P1.3
TEST
Test
Test
Function
---
INACTIVE
P1.4
FIND_DEV
Find device
Find device
DISABLE, ONE TIME, CONTINOUS
---
DISABLE
P1.5
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P2._
SETPOINT
P2.0
MIN_RGE
Min setpoint range
Min. setpoint range
4.0 to 18.4
mA
4.0
P2.1
MAX_RGE
Max setpoint range
Max. setpoint range
20.0 to 5.6
mA
20.0
P2.2
CHARACT
Charact.
curve
Characteristic
curve
LINEAR, 1:25, 1:50, 25:1, 50:1, USERD
---
LINEAR
P2.3
ACTION
Valve action
Direction of action
DIRECT, REVERSE
---
DIRECT
P2.4
SHUT_CLS
Shut-off value 0%
Shut-off value 0 %
OFF, 0.1 to 45.0
%
1.0
P2.5
SHUT_OPN
Shut off value 100%
Shut-off value 100%
55.0 to 100.0, OFF
%
OFF
P2.6
RAMP UP
Set point ramp, up
Setpoint ramp (up)
OFF, 0 to 200
---
OFF
P2.7
RAMP DN
Set point ramp, down Setpoint ramp (down)
OFF, 0 to 200
---
OFF
P2.8
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P3._
ACTUATOR
P3.0
MIN_RGE
Min. of stroke range
Operating range, min.
0.0 to 90.0
%
0.0
P3.1
MAX_RGE
Max. of stroke range
Operating range, max.
100.0 to 10.0
%
100
P3.2
ZERO_POS
Zero position
Zero position
CLOCKWISE, CTCLOCKWISE
---
CTCLOCKWISE
P3.3
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P4._
MESSAGES
P4.0
TIME_OUT
Control time out
Dead band time limit
OFF, to 200
---
OFF
P4.1
POS_SW1
Position switch 1
Switching point SW1
0.0 to 100.0
%
0.0
P4.2
POS_SW2
Position switch 2
Switching point SW2
0.0 to 100.0
%
100.0
P4.3
SW1_ACTV
Switchpoint 1 enable
Active direction SW1
FALL_BEL, EXCEED
---
FALL_BEL
P4.4
SW2_ACTV
Switchpoint 2 enable
Active direction SW2
FALL_BEL, EXCEED
---
EXCEED
P4.5
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P5._
ALARMS
P5.0
LEAKAGE
Leakage detection
Leakage to actuator
ACTIVE, INACTIVE
---
INACTIVE
P5.1
SP_RGE
Setpoint rng monitor
Outside the setpoint range
ACTIVE, INACTIVE
---
INACTIVE
P5.2
SENS_RGE
Sens. range monitor
Operating range exceeded ACTIVE,
INACTIVE
---
INACTIVE
P5.3
CTRLER
Controller monitor
Controller inactive
ACTIVE, INACTIVE
---
INACTIVE
P5.4
TIME_OUT
Control time out
Dead band time limit
ACTIVE, INACTIVE
---
INACTIVE
P5.5
STRK_CTR
Stroke counter
Movement counter
ACTIVE, INACTIVE
---
INACTIVE
P5.6
TRAVEL
Travel counter
Travel counter
ACTIVE, INACTIVE
---
INACTIVE
P5.7
EXIT
Return
Return to operating level
Function
---
NV_SAVE