![ABB TZIDC-200 Operating Instruction Download Page 50](http://html1.mh-extra.com/html/abb/tzidc-200/tzidc-200_operating-instruction_3460595050.webp)
50
TZIDC-200, TZIDC-210, TZIDC-220
DIGITAL POSITIONER | 42/18-85-EN REV. E
… 10 Operation
… TZIDC-210, -220 parameter overview
Parameter Display
Function
Possible parameter setting
Unit
Factory setting
P7.5 GOPULS
DOWN
Go pulse, down
0 to 200
msec
0
P7.6 Y-OFS
UP
Y offset, up
Y offset (up)
Y-Min to 100.0
%
40.0
P7.7 Y-OFS
DN
Y offset, down
Y offset (down)
Y-Min to 100.0
%
40.0
P7.8
---
---
P7.9 TOL_BAND
Tolerance band (zone)
Tolerance band (zone)
0.3 to 10.0
%
0.8
P7.10 TEST
Test Test
Function
---
INACTIVE
P7.11 EXIT
Return
Return to operating level
Function
---
NV_SAVE
P8._, P9._,
P10._
P11._
FS / IP
P11.0 FAIL_POS
Save position
Safe position ACTIVE,
INACTIVE
---
INACTIVE
P11.1 FACT_SET
Factory setting
Factory setting
Function
---
---
P11.2 IP-TYP
I/P module type
Type of l/P module
NO_F_POS,F_SAFE_1,F_SAFE_2,
F_FREEZE1, F_FREEZE2
--- NO_F_POS
P11.3 EXIT
Return
Return to operating level
Function
---
---
* Activation by ABB Service only
Note
For detailed information on the parameterization of the device, consult the associated configuration and parameterization
instructions.