12 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1
2.2
KNX Power Supply with diagnostics, 640/320 mA, MDRC
KNX power supplies generate and
monitor the KNX system voltage (SELV).
The bus line is decoupled from the power
supply by an integrated choke.
Bus current, bus voltage, overload and
other messages can be sent via KNX for
monitoring and diagnostic purposes.
The voltage output is short-circuit and
overload protected.
The LEDs indicate the bus current
consumption and the status of the line or
device.
Device type SV/S 30.640.5.1 has an
additional 30 V DC short-circuit and
overload protected voltage output that
can be used to power an additional bus
line (in combination with a separate
choke).
2.2.1
Technical data
Supply
Supply voltage U
s
100 – 240 V AC, 50/60 Hz
(85…265 V AC)
Power consumption
- SV/S 30.320.2.1
- SV/S 30.640.5.1
Normal operation
Maximum
12.5 W
30 W
24 W
55 W
Power loss
- SV/S 30.320.2.1
- SV/S 30.640.5.1
Normal operation
Maximum
2.5 W
6 W
4 W
9 W
Outputs
KNX voltage output I
1
Rated voltage U
N
Minimum distance between 2 SV/S in one line
1 line with integrated choke
30 V DC +1/-2 V, SELV
200 m (KNX bus line)
Voltage output I
2
(SV/S 30.640.5.1 only)
Rated voltage U
N
without choke
30 V DC +1/-1 V, SELV
The voltage output without choke may only be
used to power an additional bus line in
combination with a separate choke.
Current
- SV/S 30.320.2.1
- SV/S 30.640.5.1 (total current I
1
and I
2
)
Rated curr.
Overload curr.
Short-circuit curr.
I
N
I
Ovl
I
Sc
320 mA
0.5 A
0.8 A
640 mA
0.9 A
1.4 A
Power failure buffering time
200 ms
Connections
KNX
Bus connection terminal
Mains voltage input
Screw terminal
0.2…2.5 mm
2
fine-strand
0.2…4 mm
2
solid
Tightening torque
Maximum 0.6 Nm
2
C
D
C
0
7
1
01
7
S
00
1
3