Start-up
SV/S xx.xxx.x.1 | 2CDC501049D0201 Rev. A 25
3.4.2
Communication objects, General
No.
Function
Communication object name
Data type
Flags
0
In Operation
General
1 bit
DPT 1.002
C, R, T
The communication object is enabled if
send value 0/1 cyclically
is selected for the parameter
Send communication object
"In operation"
in the
General
parameter window.
In order to regularly monitor the presence of the device on the KNX, an in-operation monitoring telegram can be sent
cyclically on the bus.
As long as the communication object is activated and has a group address has been assigned, it sends a parameterizable
in-operation telegram cyclically.
1
Request status/measured values
General
1 bit
DPT 1.017
C, W
If this communication object receives a telegram with the value 0 or 1 (depending on parameterization), the measured
values of communication objects 2-7 are sent.
Telegram value
1/0 = Request status values
2
Bus voltage U
n
Measured value
4 byte
DPT 14.027
C, R, T
On request, the device uses this communication object to send the bus voltage U
n
to the device in V. Object value is
updated every second.
3
Bus current I
1
(only with SV/S 30.640.5.1)
Bus current I
(only with SV/S 30.320.2.1)
Measured value
4 byte
DPT 14.019
C, R, T
On request, the device uses this communication object to send the bus voltage U
n
to the device in A. Object value is
updated every second.
4
Current voltage output I
2
(only with SV/S 30.640.
5
.1)
Measured value
4 byte
DPT 14.019
C, R, T
On request, the device uses this communication object to send the current I
2
on the voltage output in A. Object value is
updated every second.
5
Total current I
(only with SV/S 30.640.
5
.1)
Measured value
4 byte
DPT 14.019
C, R, T
On request, the device uses this communication object to send the total current I (I
1
+ I
2
) in A. Object value is updated
every second.
6
4*
Total current I > Rated current I
n
(640 mA)
(only with SV/S 30.640.
5
.1)
Bus current > Rated current In (320 mA)
(SV/S 30.320.
2
.1)
Status value
1 bit
DPT 1.005
C, R, T
The device uses this communication object to report whether the rated current has been exceeded. If the rated current is
exceeded for 10 seconds then a telegram with the value 1 is sent. The value is immediately reset to 0 when the rated
current falls below the limit value. The object value is sent when there is a change, and on request.
Telegram value:
0 = Bus current < Rated current I
N
SV/S 30.320.2.1: I
N
< 315 mA
SV/S 30.640.5.1: I
N
< 630 mA
1 = Bus current > Rated current I
N
SV/S 30.320.2.1: I > 320 mA for longer than 10 s
SV/S 30.640.5.1: I > 640 mA for longer than 10 s
* Object no. for SV/S 30.320.2.1