ABB i-bus
KNX
Device technology
18 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1
2.2.5
Mounting and installation
Accessibility to the device for the purpose of operation, testing, visual inspection, maintenance and repair
must be provided compliant to VDE 0100-520.
Commissioning requirements
To commission the device you will need a PC with ETS, a connection to the ABB i-bus
®
,
e.g. via a KNX interface, and a supply voltage of 110/230 V.
Mounting
Mounting and commissioning may only be carried out by electrical specialists. The appropriate standards,
directives, regulations and specifications should be observed when planning and setting up electrical
installations.
Protect the device from moisture, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
Supplied state
The device is supplied with the physical address 15.15.255.
The application program is pre-installed. It is therefore only necessary to load group addresses and
parameters during commissioning.
However, the complete application program can be reloaded if required. Downloads may take longer after
a change of application program, an interrupted download or after unloading a device.
Assignment of the physical address
The assignment and programming of the physical address is carried out in ETS.
The device features a programming button for assignment of the physical device address. The red
Programming
LED lights up after the button has been pushed. It goes off as soon as ETS has assigned
the physical address or the
Programming
button is pressed again.
Cleaning
If devices become dirty, they can be cleaned using a dry cloth. Should a dry cloth not remove the dirt, they
can be cleaned using a slightly moistened cloth and soap solution. Corrosive agents or solutions should
never be used.
Maintenance
The device is maintenance-free. No repairs should be carried out by unauthorized personnel if damage
occurs, e.g. during transport and/or storage. The warranty expires if the device is opened.