ABB i-bus
KNX
Start-up
24 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1
3.4
Communication objects
3.4.1
Summary of communication objects
CO
No.
Function
Name
Data Point
Type (DPT)
Length
Flags
C
R
W
T
A
0
In Operation
General
DPT 1.002
1 bit
x
x
x
1
Request status/measured values
General
DPT 1.017
1 bit
x
x
2
Bus voltage U
N
Measured value
DPT 14.027
4 byte
x
x
x
3
Bus current I
1
(only with SV/S 30.640.5.1)
Bus current I (only with SV/S 30.320.2.1)
Measured value
DPT 14.019
4 byte
x
x
x
4
Current voltage output I
2
(only with SV/S 30.640.5.1)
Measured value
DPT 14.019
4 byte
x
x
x
5
Total current I
(only with SV/S 30.640.5.1)
Measured value
DPT 14.019
4 byte
x
x
x
6
Total current I > Rated current I
n
(640 mA)
(only with SV/S 30.640.5.1)
Bus current > Rated current I
n
(320 mA)
(only with SV/S 30.320.2.1)
Status value
DPT 1.005
1 bit
x
x
x
7
Overload I > I
max
Status value
DPT 1.005
1 bit
x
x
x
8
Trigger bus reset
General
DPT 1.017
1 bit
x
x
* CO = communication object