ABB i-bus
®
KNX
Device technology
8 2CDC501049D0201 Rev. A | SV/S xx.xxx.x.1
Protection class
II
EN 61 140
Isolation category
Overvoltage category
Pollution degree
III under EN 60 664-1
2 under EN 60 664-1
Temperature range
Operation
Storage
Transport
-
5 °C…+45 °C
-25…+55 °C
-25…+70 °C
Ambient conditions
Maximum air humidity
93 %, no condensation allowed
Design
Modular installation device (MDRC)
Modular installation device, Pro
M
Main dimensions (H x W x D)
90 x 72 x 64.5 mm
Mounting width
4 x 18 mm modules
Mounting depth
64.5 mm
Mounting
On 35 mm mounting rail
EN 60 715
Mounting position
As required
Weight
Approx. 0.25 kg
Housing, color
Plastic housing, gray
Approvals
KNX under EN 50 090-1, -2
CE mark
In accordance with the EMC guideline and low
voltage guideline
Important
If the device overheats due to extended overload (> 100 °C in housing) it switches off automatically.
The LED is off. The device can be switched on again only after it has been disconnected from the mains
for 60 seconds and has cooled to operational temperature internally.
Eliminate the cause of the overload before switching back on.
When commissioning the device, ensure that the rated current is not continuously exceeded.
The voltage output without choke ( I
2
) is not electrically isolated from the KNX voltage output (I
1
). It may
only be used to power an additional bus line in combination with a separate choke. It may not,
for example, be used to power IP devices (see SELV guidelines).
Devices are designed for continuous operation. They are not approved for frequent switching on and off.