Standard Power Supply, 640/320/160 mA, MDRC 

 

 

KNX power supplies generate and 
monitor the KNX system voltage (SELV). 
The bus line is decoupled from the power 
supply by an integrated choke.  

The voltage output is short-circuit and 
overload protected.  

The two-color LED indicates device 
output status. 

Device type SV/S 30.640.3.1 has an 
additional 30 V DC short-circuit and 
overload protected voltage output that 
can be used to power an additional bus 
line (in combination with a separate 
choke). 

 

 
 

2.1.1 

Technical data 

Supply  

Supply voltage U

s

 

100 – 240 V AC, 50/60 Hz 
(85…265 V AC)  

 

Power consumption  

- SV/S 30.160.1.1 

- SV/S 30.320.1.1 

- SV/S 30.640.3.1 

Normal operation 

Maximum 

6.6 W 

 

21 W 

12.5 W 

 

30 W 

24 W 

 

55 W 

 

Power loss  

- SV/S 30.160.1.1 

- SV/S 30.320.1.1 

- SV/S 30.640.3.1 

Normal operation 

Maximum 

1.8 W 

 

4.4 W 

2.5 W 

 

6 W 

4 W 

 

9 W 

Outputs 

KNX voltage output I

1

 

Rated voltage U

N

 

Minimum distance between 2 SV/S in one line 

1 line with integrated choke 

30 V DC +1/-2 V, SELV 

200 m (KNX bus line) 

 

Voltage output I

2

 (SV/S 30.640.3.1 only) 

Rated voltage U

N

 

without choke 

30 V DC +1/-1 V, SELV 

The voltage output without choke may only be 
used to power an additional bus line in 
combination with a separate choke. 

 

Current 

 

- SV/S 30.160.1.1 

- SV/S 30.320.1.1 

- SV/S 30.640.3.1 (total current I

1

 and I

2

Rated curr. 

Overload curr. 

Short-circuit curr. 

I

N

 

I

Ovl

 

I

Sc

 

160 mA 

0.3 A 

0.5 A 

320 mA 

0.5 A 

0.8 A 

640 mA 

0.9 A 

1.4 A 

 

Power failure buffering time 

200 ms  

Connections 

KNX 

Bus connection terminal 

 

Mains voltage input 

Screw terminal 

0.2…2.5 mm

2

 fine-strand 

0.2…4 mm

2

 solid 

 

Tightening torque 

Maximum 0.6 Nm 

Operating and display elements 

LED status (two-colored green/red) 

Green: I < I

Ovl

 

Red: overload. 

Red, flashing: short-circuit 

Degree of protection 

IP 20 

EN 60 529 

2

C

D

C

 07

1

 0

04

 S

0

01

4

 

Summary of Contents for SU/S 30.640.1

Page 1: ... PRODUCT MANUAL ABB i bus KNX SV S KNX Power Supplies ...

Page 2: ......

Page 3: ...ting and installation 11 2 2 KNX Power Supply with diagnostics 640 320 mA MDRC 12 2 2 1 Technical data 12 2 2 2 Connection schematic 15 2 2 3 Dimension drawing 16 2 2 4 Operating and display elements 17 2 2 5 Mounting and installation 18 3 Start up 19 3 1 Overview 19 3 2 Conversion of previous application program versions 20 3 2 1 Procedure 20 3 3 Parameters 21 3 3 1 Parameter window General 22 3 ...

Page 4: ......

Page 5: ... and enables them to communicate 1 1 Using the product manual This manual provides detailed technical information about the power supplies and how to mount and program them Device application is explained using examples This manual is subdivided into the following sections Section 1 General Section 2 Device technology Section 3 Commissioning Section 4 Planning and application Section A Appendix ...

Page 6: ...tes and safety instructions are represented as follows in this manual Please note Tips for usage and operation Examples Application examples installation examples programming examples Important These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury Caution These safety instructions are used as soon as there is danger of a malfunction without...

Page 7: ...0 30 KNX rated current in mA 160 320 640 320 640 640 Type of installation MDRC MDRC MDRC MDRC MDRC MDRC Mounting width in space units 4 4 4 4 4 8 Integrated choke Short circuit and overload monitoring Mains failure back up time in ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms without battery Mains failure back up time If used with a sealed lead acid battery e g AM S 12 1 SAK 7 2 x SAK 7 in parallel...

Page 8: ......

Page 9: ...1 1 SV S 30 320 1 1 SV S 30 640 3 1 Normal operation Maximum 1 8 W 4 4 W 2 5 W 6 W 4 W 9 W Outputs KNX voltage output I1 Rated voltage UN Minimum distance between 2 SV S in one line 1 line with integrated choke 30 V DC 1 2 V SELV 200 m KNX bus line Voltage output I2 SV S 30 640 3 1 only Rated voltage UN without choke 30 V DC 1 1 V SELV The voltage output without choke may only be used to power an ...

Page 10: ... 50 090 1 2 CE mark In accordance with the EMC guideline and low voltage guideline Important If the device overheats due to extended overload 100 C in housing it switches off automatically The LED is off The device can be switched on again only after it has been disconnected from the mains for 60 seconds and has cooled to operational temperature internally Eliminate the cause of the overload befor...

Page 11: ...ology SV S xx xxx x 1 2CDC501049D0201 Rev A 9 2 1 2 Connection schematic 1 Bus connection terminal 2 Label carrier 3 Power supply connection Us 4 Status LED 5 Voltage output without choke I2 SV S 30 640 3 1 only 2CDC072007F0013 ...

Page 12: ...ABB i bus KNX Device technology 10 2CDC501049D0201 Rev A SV S xx xxx x 1 2 1 3 Dimension drawing 2CDC072013F0013 ...

Page 13: ...20 Mounting Mounting and commissioning may only be carried out by electrical specialists The appropriate standards directives regulations and specifications should be observed when planning and setting up electrical installations Protect the device from moisture dirt and damage during transport storage and operation Only operate the device within the specified technical data The device should only...

Page 14: ...ltage Us 100 240 V AC 50 60 Hz 85 265 V AC Power consumption SV S 30 320 2 1 SV S 30 640 5 1 Normal operation Maximum 12 5 W 30 W 24 W 55 W Power loss SV S 30 320 2 1 SV S 30 640 5 1 Normal operation Maximum 2 5 W 6 W 4 W 9 W Outputs KNX voltage output I1 Rated voltage UN Minimum distance between 2 SV S in one line 1 line with integrated choke 30 V DC 1 2 V SELV 200 m KNX bus line Voltage output I...

Page 15: ...ategory Overvoltage category Pollution degree III under EN 60 664 1 2 under EN 60 664 1 Temperature range Operation Storage Transport 5 C 45 C 25 55 C 25 70 C Ambient conditions Maximum air humidity 93 no condensation allowed Design Modular installation device MDRC Modular installation device Pro M Main dimensions H x W x D 90 x 72 x 64 5 mm Mounting width 4 x 18 mm modules Mounting depth 64 5 mm ...

Page 16: ... the device overheats due to extended overload 100 C in housing it switches off automatically All LEDs are OFF The device can be switched on again only after it has been disconnected from the mains for 60 seconds and has cooled to operational temperature internally Eliminate the cause of the overload before switching back on When commissioning the device ensure that the rated current is not contin...

Page 17: ... connection terminal 2 Programming button and LED red 3 Label carrier 4 Reset button and LED red 5 Comm error LED yellow 6 Telegr LED yellow 7 Power supply connection Us 8 UN OK LED green 9 I Imax LED red 10 Bus current LED 7 x yellow 11 Voltage output without choke I2 SV S 30 640 5 1 only 2CDC072001F0013 ...

Page 18: ...ABB i bus KNX Device technology 16 2CDC501049D0201 Rev A SV S xx xxx x 1 2 2 3 Dimension drawing 2CDC072004F0013 ...

Page 19: ...low 190 mA for at least 110 ms LED No SV S 30 320 2 1 SV S 30 640 5 1 Indicator value mA Indicator value mA 7 350 700 6 300 600 5 250 550 4 200 400 3 150 300 2 100 200 1 50 100 Triggers and indicates a bus reset This function can be triggered only when mains voltage is applied Operating one line with two power supplies when the mains supply fails the Reset button on the affected device does not fu...

Page 20: ...dress 15 15 255 The application program is pre installed It is therefore only necessary to load group addresses and parameters during commissioning However the complete application program can be reloaded if required Downloads may take longer after a change of application program an interrupted download or after unloading a device Assignment of the physical address The assignment and programming o...

Page 21: ...are off and the Reset button does not function This is also the case when the device is unloaded ETS However the output voltage is generated irrespective of the indicators 3 1 Overview The ABB i bus KNX SV S 30 640 5 1 and SV S 30 320 2 1 power supplies have extended features for monitoring and diagnostics The table below gives an overview of functions the values that can be queried and the status...

Page 22: ...onversion function can still be useful to transfer the parameterization settings and group addresses of one device to another of the same type 3 2 1 Procedure Import the current VD file into ETS and add a product to the project using the current application program After you have parameterized a device you can transfer the settings to a second device For this purpose the devices must already be av...

Page 23: ...s that can be queried ETS is required for this programming The application program is available in ETS under ABB System devices Power Supplies The following section describes the parameters of the application program Parameter windows are structured dynamically so that further parameters may be enabled depending on the settings and the function The default values of the parameters are underlined e...

Page 24: ... Here the time interval at which the communication object In operation No 0 cyclically sends a telegram is set Enable communication object Request status measured values 1 bit Options no yes This communication object is used for requesting status and measured values If it receives a telegram with the value 0 or 1 depending on parameterization measured values communication objects 2 5 are sent via ...

Page 25: ...s after a change The status values are sent after a change on request The status values are sent after a request after a change or request The status values are sent after a change or a request Enable communication object Trigger bus reset 1 bit Options no yes This parameter enables the communication object to trigger a bus reset which shorts the bus line for 20 seconds yes The 1 bit communication...

Page 26: ... only with SV S 30 640 5 1 Bus current I only with SV S 30 320 2 1 Measured value DPT 14 019 4 byte x x x 4 Current voltage output I2 only with SV S 30 640 5 1 Measured value DPT 14 019 4 byte x x x 5 Total current I only with SV S 30 640 5 1 Measured value DPT 14 019 4 byte x x x 6 Total current I Rated current In 640 mA only with SV S 30 640 5 1 Bus current Rated current In 320 mA only with SV S...

Page 27: ...V S 30 320 2 1 Measured value 4 byte DPT 14 019 C R T On request the device uses this communication object to send the bus voltage Un to the device in A Object value is updated every second 4 Current voltage output I2 only with SV S 30 640 5 1 Measured value 4 byte DPT 14 019 C R T On request the device uses this communication object to send the current I2 on the voltage output in A Object value i...

Page 28: ...hysteresis SV S 30 640 5 1 IOvl 900 mA 5 hysteresis Telegram value 0 no overload LED I Imax is OFF SV S 30 320 2 1 I 475 mA SV S 30 640 5 1 I 855 mA 1 overload LED I Imax is ON SV S 30 320 2 1 I 525 mA SV S 30 640 5 1 I 950 mA 8 6 Trigger bus reset General 1 bit DPT 1 017 C W This communication object triggers a reset for 20 seconds The bus line is disconnected from the output voltage and shorted ...

Page 29: ...ce with the connection schematic below Please note The voltage output without choke may not be used for other purposes e g for connecting sensors to a binary input because in the event of an error on the voltage output e g a short circuit the power supply and therefore the whole KNX line connected to it will fail The voltage output without choke I2 is not electrically isolated from the KNX voltage...

Page 30: ...r supply Reset via bus connection terminal Pull off the device s bus connection terminal for approx 20 seconds Reset via button On type SV S 30 640 5 1 and SV S 30 320 2 1 power supplies a reset can be carried out using the Reset button To reset the device press the Reset button on the front for 2 seconds Pressing the button again during a reset has no effect no reaction no retrigger no interrupt ...

Page 31: ...n short circuit and overload Description Recommendation ON OFF Device operating normally OFF ON Current limiting active Rectify cause of short circuit or reduce number of bus devices until there is no longer an overload and only the green UN OK LED is lit ON ON Output overloaded Reduce number of bus devices until there is no longer an overload and only the green UN OK LED is lit OFF OFF No mains s...

Page 32: ......

Page 33: ...66 8 P2 0 25 1 SV S 30 320 1 1 KNX Power Supply 320 mA MDRC 2CDG110166R0011 90619 7 P2 0 25 1 SV S 30 640 3 1 KNX Power Supply 640 mA MDRC 2CDG110167R0011 90621 0 P2 0 25 1 SV S 30 320 2 1 KNX Power Supply with diagnostics 320 mA MDRC 2CDG110145R0011 83766 8 P2 0 26 1 SV S 30 640 5 1 KNX Power Supply with diagnostics 640 mA MDRC 2CDG110146R0011 86669 9 P2 0 26 1 SU S 30 640 1 Uninterruptible KNX P...

Page 34: ...ABB i bus KNX Appendix 32 2CDC501049D0201 Rev A SV S xx xxx x 1 Notes ...

Page 35: ......

Page 36: ...ent without prior notice With regard to purchase or ders the agreed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or pos sible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations con tained therein Any reproduction disclosure to third par ties or utilization of this contents in...

Reviews: